Xuân Phương, Hanoi
hvac@hrt.vnContact us
HVAC GREEN – HVAC equipment, spare parts and solutions Sales hotline0995.895.555 Cart0

Dew point in HVAC: what causes condensation and how to prevent it

Machine-translated from Vietnamese. Read the original in Vietnamese

What is dew point HVAC? Causes of condensation and How to Treat it

Air duct, AHU, FCU or chilled-water pipe lines appear watery unlikely to be due to leakage. A common cause is a surface temperature lower than the dew point of air. Properly understanding Dew Point helps identify the cause, treat thermal insulation and control humidity effectively.

What is dew point HVAC?

Dew point, English is Dew Point, is the temperature at which air reaches steam saturation.

When a cold surface has a temperature equal to or below the dew point of the surrounding air, water vapor in the air is likely to condense into water droplets on that surface.

In HVAC system, the principle can be understood simply:

Surface Temperature > Dew Point → Normally non-condensation

Surface Temperature ≤ Dew Point → There is a risk of water condensation

Therefore, the dew point is not itself a “HVAC error”

This is a physical phenomenon.

The problem only appears when the design, construction or operation conditions cause the temperature of the cold surface to drop below the environmental dew point.

Cold surfaces often have to control the dew point

In an HVAC installation, the risk of condensation is usually concentrated at:

  • Air duct refrigeration supply.
  • Sugar chilled-water pipe Chiller.
  • Valves and waterway accessories.
  • Flanges.
  • AHU case.
  • FCU housing.
  • Air outlet level.
  • The wind box.
  • Plenum.
  • Condensate.
  • The mount.
  • Point through the wall.
  • Thermal bridge sites.

The more cold surfaces exposed to high humidity air, the greater the risk of condensation.

What is a dew point different from relative humidity?

These are two commonly misleading parameters.

Relative humidity – RH expresses the ratio of the amount of water vapor present in the air to the maximum amount of water vapor that the air can contain at that temperature.

Meanwhile, Dew Point indicates the temperature at which air begins to reach saturation.

Since RH varies with temperature, only one parameter is considered:

  • RH = 55%.
  • RH = 60%.
  • RH = 70%.

It's not enough to tell if a surface is condensation - prone.

HVAC engineers need to answer two questions:

What is the dew point of the current air?

and...

What is the actual temperature of the cold surface?

Then the risk of condensation can be accurately assessed.

Simple example of dew point in HVAC

Assume the surface temperature of an air duct segment is about:

17°C

If ambient air condition has dew point:

14°C

then the pipe surface is still higher than the dew point and normally no water appears.

But when hot humid weather or outdoor air gets into the area of the engineering ceiling causes the dew point to increase:

20°C

while the tube surface remains at about:

17°C

then the condensation conditions have appeared.

This explains why the same system:

  • Dry season without condensation.
  • The season of condensation.
  • Daytime is normal.
  • At night or early in the morning appear water.
  • Previously not occurred but after a period of operation again arose.

Not necessarily the device has “broken down”

The humid heat conditions of the environment may have changed.

The most condensation-easiest locations in HVAC systems

Air duct refrigeration supply

Air levels typically have a lower temperature than the environment.

If thermal insulation is not thick enough, torn, exposed or not sealed, the outer surface temperature of the air duct may be reduced.

When this temperature is lower than the dew point, water will appear.

The locations need special attention:

  • Air duct joint.
  • Flanges.
  • The door.
  • The mount.
  • The wall passage.
  • Connect to AHU/FCU.
  • Rear air outlet.

Sugar Chilled-water Pipe Chiller

CHWSs typically have fairly low temperatures so require insulation control and vapor suppression is important.

Points where problems are more likely to occur include:

  • Van.
  • Co.
  • Tee.
  • Flanges.
  • The mount.
  • Coupling.
  • Structural penetration point.

A small gap in the insulator can create a localized cold spot that is sufficient to cause condensation.

AHU

AHUs have many low temperature zones such as:

  • Cooling coil.
  • Khung panel.
  • Checking door.
  • Drain pan.
  • Connect the air duct.
  • Metal frame.

If the insulation is not good, the gaskets are open, or there is a heat bridge, the outer surface of the AHU may be stagnant.

FCU

FCUs are usually located above the false ceiling.

When this happens, users usually only notice it when the water has drained to the ceiling.

Water sources can come from:

  • Thermal insulation.
  • Drain pan.
  • Drain.
  • Cold water valve.
  • The coupling.
  • FCU bodies.
  • The wind box.

So do not default to small FCUs that drain clogged water.

Air outlet level

metal air outlet in direct contact with the cold supply airflow.

If room humidity is high or a heat bridge occurs between the air outlet and the wind box above the ceiling, the aluminum surface can be reduced below the dew point.

Water will appear around the air outlet border.

8 Common Causes of HVAC System Condensation

Dew point HVAC

There are 8 groups of causes that need to be prioritized.

1.thermal insulation not enough thickness

Insufficient insulation can cause the outer surface temperature to drop.

Commonly seen at:

  • Air duct.
  • Chilled-water pipe.

2. thermal insulation is leaked

When the insulation is intermittent, the cold surface may come into direct contact with moist air.

Especially popular at:

  • Van.
  • Co.
  • Flanges.
  • The junction.

3. Non-sealed vapor compartment layer

Steam entering the insulation material can reduce the insulation effect.

The problem is often notable with chilled-water pipelines.

4. The environment humidity is too high

Increased humidity increases the dew point.

Even a previously trouble - free system can begin condensation when environmental conditions change.

5. outdoor air untreated moisture-proof fit

Outdoor winds can bring a large amount of moisture into the building.

The systems to be tested include:

  • AHU.
  • PAU.
  • FAHU.
  • DOAS.
  • ERV/HRV.

6. Outdoor hot humid air leakage

Outdoor air can enter through:

  • The doorway.
  • Shaft.
  • False ceiling.
  • Structural penetration.
  • Technical space.
  • Negative pressure area.

When exposed to cold surfaces, the risk of condensation increases rapidly.

7. Heat bridge

Metals can create a heat path through the insulation.

Common locations:

  • The mount.
  • Khung AHU.
  • Flanges.
  • Bolts.
  • Structural penetration point.

8. Inappropriate HVAC operation mode

The surface temperature may be too low for environmental conditions.

Need to check:

  • Cold water temperature.
  • Temperature supply air.
  • Airflow.
  • Setpoint.
  • Fan.
  • Damper.
  • Control strategy.

Condensation is not necessarily due to insulation

This is a very important point.

When a section of pipe with water is seen, many units immediately treat it by:

Cover it with insulation.

In some cases, this solution may work.

But in many other cases, the real cause is:

  • The humidity is too high.
  • Outdoor winds intrude.
  • Outdoor air has not processed hidden loads.
  • The room pressure is inappropriate.
  • Heat bridge.
  • Thermal insulation has moisture soaked.
  • Bad operation mode.
  • Abnormal airflow.

If the root cause is unknown, the site may be drained but another point of dehydration has arisen.

How to distinguish condensation from water leakage?

This is what you'll need to do before making any repairs.

Water leakage

The water already exists in the system.

For example:

  • Cold water line.
  • The coupling.
  • Khay condensate.
  • Drain.
  • Van.
  • Coil.

Condensation

Water is formed from water vapor in the air when it meets a surface with a temperature lower than the dew point.

Some signs that may support the assessment:

Condensation is usually distributed on cold surfaces or concentrated at the open thermal insulation point.

A leak is usually of a relatively clear source and the water may flow in a particular direction.

However, visual observation is only the first step.

To reach an accurate conclusion, measurements are still needed:

Temperature + RH + Dew Point + Surface Temperature

HVAC condensation testing process at HRT

Dew point HVAC

Instead of focusing right on the location where there is water, HRT approaches in series:

Ambient Air → Temperature & RH → Dew Point → Surface Temperature → Insulation → Air Leakage → HVAC Operation

Step 1: Retract the water position

The point where the water drops is not necessarily a source.

Water can run under:

  • Structure.
  • Air duct.
  • Thermal insulation.
  • Cable tray.
  • The ceiling.

Therefore, the actual point of origin must be traced.

Step 2: Measure temperature and RH in the correct area

If the problem occurs on the ceiling, the ceiling condition should be measured.

It is not advisable to take RH in the middle of a room and treat it as a condition of the entire engineering area.

Step 3: Determine Dew Point

Dew point can be determined through:

  • Specialized measuring equipment.
  • Psychrometric chart.
  • Moisture air calculation software.
  • Suitable BMS monitoring system.

This is an important value to compare with the surface temperature.

Step 4: Measure the surface temperature

Checking at:

  • The tube body.
  • Van.
  • Flanges.
  • The mount.
  • AHU case.
  • FCU.
  • Air outlet.
  • The wind box.

If:

Surface Temperature ≤ Dew Point

then that area has favorable conditions for condensation.

Step 5: Check thermal insulation and vapor proof layer

Not only look thickness thermal insulation.

Need to check:

  • Material quality.
  • Airtightness.
  • The coupling.
  • Vapor barrier.
  • Soaked condition.
  • Point through the wall.
  • The mount.
  • Valves and fittings.

Step 6: Find the source of moisture

If the area dew point is too high must determine where the moisture load comes from.

May be from:

  • The air is outdoors.
  • Doors are open frequently.
  • Shaft engineering.
  • Negative pressure.
  • Outdoor air.
  • Production activities.
  • The toilet area.
  • The process of using the work.

Step 7: Evaluate the whole HVAC operation mode

Condensation should not be separated from the system.

Need to check simultaneously:

  • Airflow.
  • Coil.
  • Filter.
  • Cold water temperature.
  • Temperature supply air.
  • Fan.
  • Damper.
  • AHU.
  • FCU.
  • PAU/FAHU.
  • Control system.

The ultimate goal is to identify root cause.

How to treat HVAC condensation by group of causes

Moisture Load Control

If the Dew Point is too high, focus on the source of moisture rather than just treating cold surfaces.

Retest may be required:

  • PAU.
  • FAHU.
  • DOAS.
  • AHU.
  • Outdoor air.
  • Exhaust.
  • Room pressure.
  • Possibility to handle hidden loads.

This is especially important in hot and humid climates.

Fix thermal insulation

The thermal insulation broken segments must be evaluated before repairing.

If the material has soaked in water, adding just one extra layer of plastic wrap may not be a good solution.

Ensure that:

  • Enough thickness.
  • Continuously.
  • Sealed joint.
  • No leakage at the valve.
  • No openings at the flanges.
  • Vapor barrier is properly handled.

Heat bridge treatment

If the cold spot forms at:

  • The mount.
  • Bolts.
  • Metal frame.
  • Flanges.
  • Point through the wall.

Heat transfer lines must be handled at the same location.

Increasing the overall insulation without bypassing the heat bridge may not solve the problem.

Controlling Hot Air Moisture Ingress

Testing:

  • The doorway.
  • Shaft.
  • - Chen.
  • Structural penetration.
  • Room pressure.
  • Air balance.
  • Exhaust system.
  • Outdoor air.

This is especially common in hot and humid conditions.

Setpoint reassessment

Do not arbitrarily raise the temperature of cold water or supply air just to run out condensation.

Changing the setpoint can affect:

  • Cooling capacity.
  • Possibility to handle hidden loads.
  • Room temperature.
  • Moisture.
  • Energy efficiency.

The system should be evaluated in a series:

Cooling Load → Sensible Load → Latent Load → Airflow → Dew Point → Energy

6 mistakes to avoid when dealing with condensation

Water seepage is the conclusion of a leaking pipeline

Not all water droplets come from a water system.

Instantly add insulation

Symptoms can be treated but not the cause.

RH measurement in room only

Conditions on the ceiling or machine room may be completely different.

Only check thermal insulation thickness

The quality of the joints and vapor barrier is also important.

Reduce temperature to “more powerful dehumidification”

The colder the surface, the higher the risk of descending below the Dew Point if the moisture load is not properly controlled.

Only corrects the position where water is dripping

If root cause is in your system, it's easy to re-trigger the problem elsewhere.

Why condensation can increase operational costs?

Condensation is not only aesthetically pleasing.

Bare and Finished

Water can do:

  • Bare tube.
  • Paintball.
  • Plasterboard burns.
  • Damaged interior materials.

Increased risk of mold

Prolonged moist areas are a good environment for mold to grow.

Degrade thermal insulation efficiency

A waterproofing seal can reduce insulation.

As the insulation efficiency decreases, the more likely the surface temperature is to drop and the problem can get worse.

Corrosion Equipment

Water in long-term contact with:

  • Sun.
  • Steel.
  • Bolts.
  • The rack.
  • Flanges.

can increase the risk of corrosion.

Increased energy loss

When insulation is no longer effective, thermal load penetration increases.

The equipment must work more to maintain the design conditions.

Prevention of condensation right from the design stage

The most effective solution is not to fix after the water appears but to control the risk from the beginning.

Design stage

Need to consider:

  • Outdoor moist heat conditions.
  • Outdoor air.
  • Latent load.
  • Cold water temperature.
  • Supply Air Temperature.
  • Technical ceiling space.
  • Thermal insulation thickness.
  • Vapor barrier.
  • The rack location.
  • Heat bridge.
  • Room pressure.

Construction phase

Special Test:

  • Van.
  • Co.
  • Tee.
  • Flanges.
  • The mount.
  • The junction.
  • Point through the wall.
  • The door.

A system that is well thermal insulated over most of its length can still condensate because of a few exposed sites.

Operation phase

Periodic monitoring is required:

  • Temperature.
  • RH.
  • Dew Point.
  • Airflow.
  • Filter.
  • Coil.
  • Thermal insulation.
  • Outdoor air.
  • BMS.
  • Setpoint.

Dew point in ESG standard GREEN HVAC strategy

Controlling the Dew Point is not about simply dealing with small drops of water to the ceiling.

A prolonged condensation system can reflect problems with:

  • Design.
  • Thermal insulation.
  • Manage moisture load.
  • Air distribution.
  • Outdoor air.
  • Operation.
  • Controls.

These issues are directly related to:

Energy → Maintenance → Equipment Life → Indoor Environment

So in the approach ESG Standard GREEN HVACsolutions should be simultaneously aimed at:

Humidity heat stability → Limit energy loss → Protect equipment → Reduce long-term operation cost.

Conclusion

When air duct, AHU, FCU, air outlet or chilled-water pipe line appears water, do not rush to conclude that the system is leaking.

Let's check logically:

Temperature → RH → Dew Point → Surface Temperature → Insulation → Moisture Source → HVAC Operation

If:

Surface Temperature ≤ Dew Point

then the risk of condensation has formed.

Understanding the right dew point helps operation team and project owner:

  • Determine the right cause.
  • Avoid correcting errors.
  • Reduces damage to ceilings and materials.
  • Control mold.
  • Protect your HVAC system.
  • Reduce energy loss.
  • Optimize long-term operation costs.

🌿 HRT – ESG GREEN HVAC

Source: Publisher’s English edition · Vietnamese original on doanvanhoang.com