Error code E1-1 Daikin VRV: Faulty outdoor unit board, cause and solution
Machine-translated from Vietnamese. Read the original in Vietnamese

E1-1 is a special error on Daikin VRV system because it is related to the control area of the outdoor unit. However, the fault code should not be seen and replaced immediately. It is necessary to check the fault code, operation history, power supply, connection wires and control board in the correct order.
What does E1-1 Daikin VRV error code mean?
When Daikin VRV central air conditioning system appeared E1-1 error code, the operator often thinks immediately that the outdoor unit control board is broken.
This is not a good conclusion.
E1 code belongs to the warning group related to abnormalities in the area Main PCB – control board of outdoor unitHowever, before deciding to repair or replace PCBs, technicians should further determine:
- The exact model of outdoor unit.
- Sub-code is displaying.
- Which module in the outdoor unit has an error.
- Previous error history.
- Power status.
- PCB wires and connectors.
- Signs of burning, oxidation or moisture at the electrical box.
The key principle is:
Do not replace components before identifying the correct cause.
Especially with VRV system with large equipment value, misdiagnosis can increase costs but still not treat the root cause.
Common Manifestations of E1-1 Errors
Error E1-1 does not always manifest the same way.
Depending on the system status, users may experience one or more of the following phenomena:
Indoor unit still has power but not cooling
Remote is still on and receiving commands, but outdoor unit does not operate or does not generate sufficient cooling capacity.
If an outdoor unit is serving multiple indoor units, the scope of influence can be quite wide.
Outdoor unit not booting
The device receives commands but compressor or outdoor unit fan does not work.
The controller then noted the error.
The system has been running for a while and then it stops.
The computer may start normally, but after a period of time will shut down and report an error.
In this case, it is necessary to check the PCB, electrical connection and previous errors.
Reset finished but error keeps coming back
Shutting down and re-powering the system sometimes makes it run temporarily.
But if E1-1 reappears:
reset is no longer a disposal option.
Reset only changes the current state of the system, not eliminates the cause of the error.
5 groups of causes should be checked for E1-1 errors
Instead of starting with replacement of the bowel, HRT recommends categorizing causes into 5 groups.
1. PCB main outdoor unit abnormal
The main PCB is responsible for processing many important control signals of the outdoor unit.
Bo may have problems due to:
- Degraded electronic components.
- Short circuit.
- Superheat.
- Moisture.
- Oxidation.
- Abnormal voltage.
- Insect invasion.
Both physical and operational signs should be observed when testing.
2. Jack or PCB connector contact not good
A loose connector can also cause control failure.
Need to check:
- Jacks.
- Wire harness.
- Head and bone.
- Connector.
- Signs of heat burn.
- Oxidation signs.
This is a simple step, but it's especially important.
3. Power supply to outdoor unit is unstable
VRV's electronics and inverters require consistent power quality.
It should be noted:
- Voltage.
- Pha.
- The bridge.
- Protective equipment.
- Point of contact.
- Head and bone.
- Heat emission at the connection point.
Don't just measure the power in the mainframe and then conclude it is coming from a normal source.
4. Installation environment influences the electrical box
Outdoor units are usually located outdoors or in semi-open technical areas.
Factors such as:
- Rainwater.
- Toilet water.
- Moisture.
- Dust.
- Insects.
- Rats.
are both able to impact the PCB and electrical connector.
5. Instant error or interference in the system
In some cases, a bug may appear.
The technician may need to disconnect the power, check it, and restart it according to the proper procedure for verification.
If the error returns, further diagnosis is needed.
E1-1 Fault Rapid Diagnostic Table
| Realistic phenomena | Priority Testing Direction |
|---|---|
| E1-1 appears immediately after power supply | PCB, connector and link wire |
| Reset the machine to restart | Monitor instant errors, interference or sources |
| E1-1 Multiple Returns | Deeply inspect Main PCB and connectors |
| PCB with Fire Mark | Identify the cause of the fire before replacing |
| Jack is loose or oxidized | Handle connector and recheck |
| Electrical Box With Moisture Mark | PCB Testing and Causes of Water Ingress |
| Multiple error codes at the same time | Read the error history before concluding |
| Multiple indoor units same cold loss | Determine the outdoor unit/module causing the error |
The 7-step process of E1-1 error testing at HRT

Step 1: Record the error code before reset
This is a step that's easy to miss.
Before impacting the device, it is necessary to record:
- Error code.
- Sub-code.
- Model.
- Serial.
- Outdoor unit failed.
- Error module.
- The time of arising.
- The error codes come with.
If the data is reset before it can be recorded, some of the data for the diagnostic may be missed.
Step 2: Check the error history
An error history may indicate that the system is experiencing a single error or repeated problem.
The technician should identify:
- How many times does E1-1 appear?
- Time between errors.
- There is a source error that appeared earlier.
- Communication error or not.
- The error occurred after a power outage or maintenance.
- Are there other modules that report the same error.
This is very important data to find the root cause.
Step 3: Securely isolate the power supply
Before opening the electrical box, it is necessary to fully carry out the electrical safety procedure.
VRV system has:
- Power circuit.
- Inverter.
- Capacitor.
- PCB.
- Various voltage levels.
Even after a power cut, some components may remain at voltage for a certain period of time.
The internal inspection must be conducted by professional persons.
Step 4: Check the PCB wire and connector
Should not remove the board immediately.
Please check in advance:
- Jacks.
- Connector.
- Link wire.
- Head and bone.
- Contact point.
- Signs of heat emission.
- Oxidation signs.
- Signs of rats or insects.
If abnormal connector is detected, it should be handled and run a retest before concluding the PCB is damaged.
Step 5: Check the power supply to outdoor unit
The power should be measured at the actual location of the device.
Technicians should pay attention to:
- Voltage level.
- The bridge.
- Aptomat.
- Contactor.
- Head and bone.
- Signs of abnormal heat.
- Power connection points.
For high-power systems, unstable power supply can significantly affect electronic component life.
Step 6: Check the Main PCB outdoor unit
After excluding external causes, new go deep into PCB.
Examples may include:
- Observe visually.
- Condition of components.
- Signs of fire.
- Oxidation.
- It's a little damp.
- Connector.
- Signals are as per technical instructions.
- Check the Service Manual for your specific model.
Do not fix or replace components in a random test.
Step 7: Powering and commissioning system
Post-processing needs for actual operation system.
Follow up:
- Outdoor unit.
- Compressor.
- Fan.
- Indoor unit.
- Ability to respond to loads.
- Error code.
- History of errors after processing.
Don't just finish the job because your computer has rebooted.
The goal is to:
confirm the system operation is stable and the error does not reappear.
E1-1 means replacing the outdoor-unit control board?
No, no, no.
This is very important for both the user and the technician.
When the fault reporting system is related to PCB, it should distinguish at least three cases:
PCB is really broken
If there are sufficient technical grounds to believe that the boron is no longer capable of operating stably, the plan for repair or replacement shall be considered.
Normal PCB but connector has problem
In case the connector or signal wire is loose, replacing the PCB does not solve the right cause.
PCB broken due to another cause
For example:
- Unusual power supply.
- Water ingress.
- Insects.
- Superheat.
If you replace the PCB without addressing the underlying cause, your new board will still be at risk of failure.
6 Common mistakes when handling E1-1 errors
Reset machine several times
Reset is not a bug fix.
If the error code repeats, a diagnosis is needed.
See E1-1 and put a new board now
This can lead to replacement of unnecessary components.
Ignore error history
An error code that occurs after a source error has different meaning than a PCB error that appears independently.
Do not check connector
This is a small detail but can determine the diagnosis.
Use other model's error code
Daikin VRV has many generations.
Sub-code and test procedures must be compared with true actual model.
Replacement of bo but not finding the root cause
This is one of the reasons errors recur after repair.
How to limit PCB outdoor unit failure recurrence?
Maintenance periodically but must check the electrical part
Maintenance VRV should not include only heat exchanger cleaning.
Need further checking:
- Electrical cabinets.
- PCB.
- The wires.
- Connector.
- Fan.
- Signs of heat emission.
- Oxidation.
- History of error codes.
A clean system is not necessarily a working electrical system.
Control the area of outdoor unit
Special note the status:
- Rainwater.
- Toilet water.
- High humidity.
- Insects.
- Rats.
- Dirt.
- Lack of ventilation.
An improper installation location can significantly reduce the life of the electronic board.
Quality Control of Power Supply
The power supply must be considered part of the HVAC system.
For large projects, attention should be paid to:
- Voltage.
- Protective equipment.
- Grounders.
- Connector.
- Quality of electrical system.
Don't focus on the cold part of the hair, but on the electrical part.
Build operation logs
For hotels, factories, offices and commercial buildings, it is recommended to save:
- Date of error.
- Error code.
- Device failure.
- Causes.
- Handling measures.
- The parts are replaced.
After a period of operation, this data becomes a very useful source of information for maintenance and troubleshooting.
HRT procedure when receiving VRV incidents
HRT approaches the problem in the direction:
Phenomenon → data → test → cause → alternative → operation confirmation.
1. Receiving phenomena
Record the problem that the customer is experiencing and the scope of influence.
2. Data collection
Check fault codes, models, history and operation conditions.
3. Zoning of causes
Analyze electrical, control, PCB, connectors and related equipment.
4. Actual measurement and inspection
Don't jump to conclusions based on experience or sense.
5. Proposed plan
Clearly distinguish:
- Something to deal with right away.
- Components to replace.
- Components do not need to be replaced.
- The cause needs fixing.
- Items to monitor.
6. commissioning and confirmation
Equipment must be tested in actual operation condition before finishing.
This is also the spirit of HRT:
Understand - Clear - Dedicated.
When to stop the system and call for technical assistance?
It is recommended to request a technical unit specializing in VRV for inspection when:
- E1-1 is constantly present.
- Reset but error returned.
- Outdoor unit does not start at all.
- Many areas experience a cooling loss.
- Abnormal impact of the ampulla.
- There's a burning smell from the power box.
- PCB with burn marks.
- The electrical box is watery or damp.
- Could not identify the error module.
If smell of burning, burning or electrical abnormalities are detected, the power should not be continued to be closed repeatedly.
FAQ – FAQ about E1-1 Error
What is the E1-1 Daikin VRV error?
E1 belongs to the group of abnormal related errors at the Main PCB of the outdoor unit on systems applying this error code.
Sub-code should be collated with the correct model and technical documentation.
Can I use air conditioner while I'm on E1-1?
If the system has stopped itself or is constantly failing, it is not recommended to try to force the operation machine.
We need to check for causes.
Does it work when I turn off the aptomat and then on again?
It is possible to make the error temporarily disappear in some cases.
But if E1-1 returns, the cause has not been addressed.
E1-1: Is Main PCB replacement required?
Could not conclude based on error code alone.
Power, wire, connector and PCB must be checked first.
Why can newly replaced boards still fail?
Because the root cause may lie in electricity, moisture, water, superheat or other environmental factors.
Should I remove the test board myself?
Don't do this without the proper equipment and expertise.
Outdoor VRV unit contains power circuit, inverter and high voltage components.
Conclusion
Error Code E1-1 outdoor-unit control board failed need to be handled in a systemic diagnostic mindset, rather than focusing on just one component.
The matching sequence is:
Error recording → reading history → power testing → wire and connector testing → PCB evaluation → cause handling → commissioning confirmation.
It's not just about getting the machine running again.
The ultimate goal is to:
identify the right cause, handle the right item and limit recurrence of errors.
HRT provides solutions for inspection, maintenance, repair and optimization of VRV/VRF central air conditioning systems for offices, hotels, factories and commercial buildings.
Right From the Start – Clear To the End – Green Sustainable.