Error Code E2-1 Daikin VRV: Cause, Check & Solution
Machine-translated from Vietnamese. Read the original in Vietnamese

The E2-1 Daikin VRV warning code indicates abnormal electrical current flow. The article analyzes the causes, signs, methods of inspection and safe and technical handling procedures.
What is the E2-1 Daikin VRV Error Code?
E2-1 Daikin VRV Error Code is a warning related to the system detecting abnormality of leakage current or electrical leakage to the ground at the outdoor unit system.
On VRV systems with multiple outdoor unit modules, sub-code can be used to identify the abnormal module. Therefore, when E2-1 appears, technicians need to determine the exact model, series and Master/Slave configuration before conducting a diagnostic.
The important thing is:
E2-1 is not immediately synonymous with compressor failure or inverter failure.
The error code only provides the initial diagnosis direction. The actual cause must be determined through system inspection.
Quick summary of E2-1 Daikin VRV fault
| Content | Information to note |
|---|---|
| Error Code | E2-1 |
| Error Group | Abnormalities related to earth leakage currents |
| Equipment to be tested | Outdoor unit VRV |
| Degree of | Need to check soon |
| Should I reset it constantly? | No |
| Can conclude compressor failure? | No |
| Need to check | Power supply, conductor, insulation, compressor, current sensor, related board |
Common signs when the system is E2-1
The operator may experience one or more of the following:
- Remote or E2-1 display controller.
- Outdoor unit shut down.
- One or more areas are no longer cooling.
- The machine went on for a while and then stopped.
- MCCB or ELCB may be involved.
- Error reappears after reset.
- The error appears after rain or when the humidity is high.
- Electrical boxes with signs of moisture, oxidation or lightning.
When errors are detected, the time of occurrence, loading conditions and accompanying error codes should be recorded for diagnostic purposes.
Is E2-1 a dangerous error?
E2-1 belongs to the incident group that should be prioritized for inspection because it is related to electrical safety and insulation capability of the equipment.
If the actual cause is grounding or insulation deterioration, the operation failure may cause:
- Continuous impact protection device.
- Loss of wires or electrical components.
- Damaged electronic board.
- Compressor effect.
- Stop the entire VRV cluster.
- Increased risk of electrical safety loss.
Don't just reset your computer and keep using it.
6 Common Causes of E2-1 Daikin VRV Error

Grounding or insulation attenuation
The current may leak to the ground when:
- The power cord is damaged insulation.
- The wire touches the metal housing.
- Jack or cos head is damp.
- Water gets into electrical components.
- Motor coils or compressor attenuation insulators.
This is a group of causes that should be checked early.
Unusual wires and connectors
After long time operation, the wires in outdoor unit can:
- Scrub the chassis.
- Cracking or aging.
- Damaged by insects or animals.
- The cosine head is loose.
- Terminal is oxidized.
- The connector jack is damp.
Before replacing the bo or compressor, it is recommended to carefully check the entire wiring.
Circuit or sensor detects leakage current
VRV system uses monitoring circuits to detect abnormal electrical conditions.
Need to check:
- Current sensor.
- Sensor connection wire.
- Connector.
- Fistula flow detector circuit.
- Related control boards.
An abnormal signal from the detection system may also produce E2-1.
Compressor attenuation of insulation capacity
Compressor is the large power load of VRV system.
The problems may be related to:
- Coil aging.
- High operation temperature lasting.
- Earlier electrical problems.
- Adverse operation environment.
- Intrinsic abnormalities of the compressor.
However:
Do not replace compressor based on E2-1 code only.
Confirmation of measurement data is required before making a decision.
Water or moisture penetration electrical box
Especially with outdoor unit put outdoor, need to check:
- Rainwater invading.
- Condensation.
- The power box is not sealed.
- Dirt combines moisture.
- Terminal is oxidized.
- The wires or boards are damp.
If the bugs usually appear after rain or humid weather, these are the groups of causes to prioritize.
Abnormal operation conditions
In some models, the troubleshooting process also needs to take into account refrigeration system conditions such as:
- Temporary liquid back.
- Refrigerant stagnation.
- Other operation abnormalities.
Therefore, when electrical examination does not detect an obvious cause, further diagnosis is required based on service manual correct model.
Should I reset when Daikin VRV says E2-1?
Do not reset it continuously.
Reset can only erase temporary fault states, but does not address the cause of the leak.
The proper process should be:
Record faults → ensure safety → zone → measurement → repair → commissioning.
Should not:
Reset → rerun → error → continue reset.
If the leakage current protection device has been affected, the cause must be determined before power is switched back on.
E2-1 Daikin VRV Fault Check 8 Step Process
Step 1: Determine the model and system configuration
Need to note:
- Model outdoor unit.
- Serial.
- Series VRV.
- Number of outdoor unit modules.
- Configure Master/Slave.
- Electrical diagram.
- Service manual matching.
This helps avoid misuse of troubleshooting processes between different VRV streams.
Step 2: Check the error history
Need to identify:
- How many times does E2-1 appear?
- Does it appear when powered on or when compressor is running?
- Is there another error code included?
- Does it happen at low load or high load?
- Did there be any electrical problems before?
Error history helps distinguish random errors and repeated errors.
Step 3: Visual inspection
Careful observation:
- Electrical box.
- Power cord.
- Compressor wire.
- Terminal.
- Jack connects.
- Grounding point.
- Signs of lightning.
- Water or moisture.
- Signs of damage from insects or animals.
Many problems can be detected right at this step.
Step 4: Check the power supply
Measurement and evaluation:
- Power voltage.
- Interphase voltage.
- Phase loss.
- Phase deflection.
- MCCB/ELCB.
- Power Terminal.
- Grounding system.
An abnormal power supply can cause the system to malfunction.
Step 5: Insulation capability test
This requires a technician with the right expertise and equipment.
Need:
- Zone each load group.
- Isolate the correct components.
- Follow the service procedure.
- Avoid measuring directly through electronic boards or inverters without proper isolation.
Mis-measurement can damage electronics.
Step 6: Test compressor
If the diagnostic data is directed towards compressor, it should be checked:
- Coil resistance.
- Insulation capacity.
- Terminal compressor.
- Connection wire.
- Operation line.
- Mechanical and electrical abnormalities.
Only replace compressor when there is sufficient technical evidence.
Step 7: Check the circuit for leakage current detection
Testing:
- Current sensor.
- Connector.
- Signal wire.
- Related control boards.
- Abnormal signal.
- Signs of disconnection or damage.
Step 8: commissioning after processing
After repair need:
- Check the wires.
- Check the terminal.
- Check the grounding.
- Power it.
- Reset error correct procedure.
- Commissioning.
- Monitor the current.
- Monitor pressure and temperature as needed.
- Check your error history.
- Monitor the system at multiple load levels.
Handover should only be done when the device is stable.
How to quickly zone E2-1 error
| Time of error | Groups to check first |
|---|---|
| As soon as powered on | Wire, Grounding, Sensor, Bore |
| When compressor starts | Compressor, wire compressor, power circuit |
| After a run time | Insulation when hot, operation condition |
| After the rain | Electrical box, terminal, conductor, humidity |
| ELCB Continuous Jumper | Fistula current, earth touch, insulation |
| Reset and error | Reset not continued, need to measure intensively |
The above table is only used to guide initial testing.
What not to do when meeting E2-1
To limit damage that may arise, it is not recommended:
- Reset repeatedly.
- Close the ELCB/MCCB repeatedly without inspection.
- Replace the inverter based on guesswork.
- The compressor failure was based on error code only.
- Measure insulation through the board before isolating the load.
- Ignore signs of water ingress or lightning.
How to limit E2-1 recurrence?
Periodic electrical test
Should be checked:
- Terminal.
- The cosmic head.
- The wire.
- Grounders.
- MCCB/ELCB.
- Electrical box.
Keep the electrical box dry and sealed
The root cause of water ingress should be addressed, not just the components.
Tracking error history
Electrical faults that occur infrequently still need to be saved to detect abnormal trends.
periodic maintenance of VRV systems
Maintenance VRV is not only hygienic heat exchanger but also have to check:
- Electrical system.
- Operation line.
- Terminal.
- Insulate.
- Outdoor unit conditions.
- Refrigeration system parameters.
When should I call a Daikin VRV?
Request a professional technician when:
- E2-1 appears repeated.
- ELCB/MCCB impact.
- The system can't start.
- It smells like burn.
- There's water in the power box.
- Wires are burnt or discolored.
- The work needs to maintain continuous operation.
Unskilled operators should not manually remove the inverter board or measure the compressor insulation.
HRT inspection and fault handling Daikin VRV E2-1
HRT provides inspection, maintenance, repair and optimization services for Daikin VRV/VRF central air conditioning systems for:
- The factory.
- The office.
- The building.
- The hotel.
- The mall.
- Commercial and industrial buildings.
With E2-1 error, the HRT's handling principle is:
Understand the right cause - measure clearly - handle it from the beginning.
HRT prioritizes to zone with technical data before suggesting replacement of bo, compressor or other components of great value.
Source: Publisher’s English edition · Vietnamese original on doanvanhoang.com