ERV or HRV? Choosing a fresh air ventilation system

Machine-translated from Vietnamese. Read the original in Vietnamese

How different is ERV and HRV? How to choose outdoor air system

HRV is primarily heat recovery inducer, while ERV can recover both heat and partial humidity. The selection should be based on outdoor air load, climate conditions, airflow, pressure drop and exhaust air quality.

Selecting ERV or HRV should not start from device name

When designing outdoor air system, the common question is:

Should I use ERV or HRV?

If you only look at the catalog, many people tend to think that ERV “higher" HRV because of the additional ability to exchange moisture.

But in reality, the right choice doesn't lie in which device has more functionality.

What should be determined in advance is:

  • How much outdoor air does the project need?
  • How hot and humid is the wind outside?
  • What are the conditions of exhaust air?
  • Is the moisture load large?
  • How many hours does the system operate?
  • Is the fan enough pressure head after adding exchanger?

The more appropriate ERV or HRV is determined from these data.

Can be briefly understood:

HRV → Focused heat recovery sensation

ERV → heat recovery sensor + moisture-related energy part

Why does outdoor air system need to recover energy?

Outdoor air is needed to maintain indoor air quality, but adds load to the air conditioning system.

When outdoor air is put into the building, HVAC system must handle:

  • The temperature.
  • Moisture.
  • Partial load ventilation.
  • Comfortable conditions of the space.

Meanwhile, exhaust air from the air conditioning room still has a portion of energy.

If discharged directly into the environment:

The energy used for cooling or heating the air will be lost.

ERV and HRV utilize exhaust air flow to pre-treat outdoor air before it enters cooling coil or subsequent treatment equipment.

Typical Chains:

Outdoor Air → ERV/HRV → AHU/DOAS → Cooling Coil → Air Conditioning

and:

Air Conditioning → Exhaust Air → ERV/HRV → Discharge

The goal is to reduce the load on the main system while ensuring airflow ventilation.

What is the principle of HRV?

HRV stands for:

Heat Recovery Ventilator

The device uses two air currents:

  • Outdoor air outdoor.
  • Exhaust air in the building.

The two streams of gas pass through the heat exchanger but are not actively mixed directly into each other.

In hot season conditions:

  • The wind outside is high temperature.
  • Exhaust air from the air conditioning room with lower temperature.

HRV uses the rest of the exhaust air to cool outdoor air before it enters the cooling coil.

Can you imagine:

Outdoor Air Heater → HRV → outdoor air heat reducer → Cooling Coil

Results:

Sensible Load ↓

Cooling coil will not have to handle the entire temperature difference from the outdoor state.

Does HRV treat humidity?

This is the most important difference when comparing ERV and HRV.

HRV follows the sensible-only principle of predominantly inductance heat exchange.

That means:

  • Outdoor air temperature can be reduced.
  • Humidity ratios can still be high.

If outdoor air is hot and humid, the rear cooling coil still has to handle most of the moisture load.

This process typically includes:

Cooling of air down to the dew point → condensate vapor condensing → moisture separation

So HRV can help reduce sensible load but does not mean the system has solved latent load.

What makes ERV different from HRV?

ERV stands for:

Energy Recovery Ventilator

ERVs also use two similar HRV wind streams.

The difference is in the energy exchange capacity.

Exchangeable ERV:

  • Sensible energy.
  • Part of the latent energy.
  • Total energy of air flow.

In hot and humid conditions:

Outdoor Air → ERV → Reduce temperature + reduce partial moisture load → Cooling Coil

Therefore, the rear cooling coil can receive air flow with lower enthalpy.

This is the reason that ERV is often included in the evaluation plan at works with:

  • Large amount of outdoor air.
  • High humidity outdoors.
  • Long operation time.
  • RH control requirements.

ERV and HRV Quick Comparison

Criteria HRV ERV
Full name Heat Recovery Ventilator Energy Recovery Ventilator
Heat recovery felt Yes Yes
Humidity Exchanger Not a primary function Yes
Reduce sensible load Yes Yes
Reduce latent load Restrictions Yes
Suitable for hot humid climate Need to evaluate moisture load Often worth considering
Did you change the cooling coil? No No
Need to calculate pressure drop Yes Yes
Need to check leakage Yes Yes

The above table shows only differences in principle.

The actual effect also depends on:

Airflow + Effectiveness + Pressure Drop + Leakage + Fan Power + Operating Hours

To choose the right one must understand thermal load and moisture load

When handling outdoor air, should not only look dry-bulb temperature.

Outdoor air loads are usually composed of two parts.

Sensible Load – thermal load sensor

It occurs when the temperature in the room and outdoors is different.

For example:

  • Outdoor: 35°C.
  • In-room: 25°C.

The HVAC system must take away the heat proportional to that difference.

Latent Load – hidden load

It occurs when the amount of water vapor in outdoor air is higher than the required level in the room.

Cooling coil must be cooling air deep enough for condensate to condense and be removed.

Hence:

Outdoor Air Load = Sensible Load + Latent Load

If sensible load is only calculated, the choice of ERV or HRV may be wrong from the start.

When does ERV have a clearer advantage?

ERV is usually worth considering when the following conditions are present.

Outdoor air accounts for a large proportion

Some constructions require large amounts of outdoor air such as:

  • The office.
  • The mall.
  • Hall.
  • School.
  • The hotel.
  • The restaurant.
  • The factory.
  • Large space.

The greater the amount of outdoor air, the more significant the ventilation load.

Hot and humid climate

When outdoor air is both hot and humidity ratio is high, the system must handle both load components.

ERV can support reduction of:

Sensible Load+Part Latent Load

Works need RH control

For spaces with humidity requirements, latent load cannot be ignored.

If ventilation air carries in large amounts of steam, the ERV can help reduce rear handling load.

Multi-hour operation system

Efficiency in recovering accumulated energy over time.

A 12 hour/day operation system will have a different energy saving problem than a system that only runs 2–3 hours.

When is HRV still a reasonable option?

HRV is not a lower - end solution than ERV.

In many systems, HRV is still appropriate if:

  • The primary goal is sensible recovery.
  • Moisture load negligible.
  • The system has its own dehumidification solution.
  • Unwanted moisture transfer.
  • Exhaust air characteristic is not suitable for ERV.
  • Investment and operation analysis showed HRV was more efficient.

What to avoid is thinking:

ERV more functions → better default

The right way should be:

Load analysis → select device

Does ERV replace cooling coil or dehumidifier?

No, no, no.

ERVs are not stand - alone refrigeration generators.

ERV only supports partial load reduction before outdoor air enters the main processing system.

The rest of the load still needs devices like:

  • Cooling coil.
  • AHU.
  • DOAS.
  • DX coil.
  • Chiller.
  • VRV/VRF.
  • Dehumidifying equipment dedicated.

Understandable:

ERV = energy recovery and pre-treatment

Not:

ERV = replacement air conditioner

7 questions to answer before choosing ERV or HRV

ERV and HRV

1. How much Outdoor Airflow?

First must determine the correct amount of outdoor air design.

Don't choose by feeling or just by room size.

2. Is Exhaust Airflow sufficient?

Energy recovery requires the proper exhaust air flow.

If:

Outdoor Air ≫ Exhaust Air

the possibility of retrieval will be limited.

3. What is Outdoor Design Condition?

Don't just check the temperature.

Need to see:

  • Dry-bulb temperature.
  • Relative humidity.
  • Humidity ratio.
  • Enthalpy.

4. Exhaust Air Condition ra sao?

Need to know:

  • The temperature.
  • Moisture.
  • Wind quality.
  • The level of pollution.

5. How much effectiveness?

Catalogue should be read properly according to:

  • Sensible effectiveness.
  • Latent effectiveness.
  • Total effectiveness.

6. How does Pressure Drop affect Fan?

Exchanger creates additional resistance.

Hence:

Pressure Drop ↑ → Static Pressure Requirement ↑

Without checking the fan, the actual airflow may decrease.

7. Is Leakage and Contamination within the limits?

This is very important factor when exhaust air has:

  • Smells.
  • Pollution.
  • A little chemical.
  • Risk of cross-contamination.

Should not choose ERV by room area

A common question is:

“What ERV airflow rate, in m³/h, does a 100 m² room need?”

Area is just a data point.

Outdoor airflow also depends on:

  • Functional.
  • Number of people.
  • Human density.
  • Ventilation standard.
  • Pollution sources.
  • Time of use.

Proper Process:

Ventilation Requirement → Airflow → Load → ERV/HRV → Fan → Control

Should not:

Area → select an available model

Pressure drop can reduce energy recovery efficiency

A device with high effectiveness does not necessarily deliver the highest energy saving.

When adding exchanger to the wind line:

Resistance ↑

The fan must create additional pressure head to maintain airflow.

Results:

Fan Power ↑

Therefore, the actual effect should be evaluated according to:

Net Energy Saving = Energy Recovered – Additional Energy Consumption

Additional power may come from:

  • Fan.
  • Motor.
  • Energy wheel.
  • Control.
  • Pressure drop.

This is why it is not recommended to look at only a number of “80% efficiency” in the catalog.

Leakage and exhaust air quality should be viewed separately

In theory, outdoor air and exhaust air are two separate lines.

But realities may arise:

  • Leakage.
  • Seal leakage.
  • Carryover.
  • Differential pressure between two gas streams.

With rotary energy wheel, special attention should be paid to carryover capability.

Not all exhaust air should pass through the energy recovery device.

Caution should be exercised with exhaust air from:

  • The bathroom.
  • The kitchen.
  • Chemical sector.
  • Smell area.
  • Space has its own particular contaminants.

Principle:

Exhaust Air Quality → previous reviews Energy Recovery

ERV and HRV selection process at HRT

ERV and HRV

HRT does not select ERV or HRV as a stand - alone device.

Devices placed in the chain:

Outdoor Air → Exhaust Air → Psychrometric Condition → ERV/HRV → AHU/DOAS → Fan → Control → Energy

Step 1: Determine the amount of outdoor air

Testing:

  • Functional.
  • Number of people.
  • Standards.
  • Flow rate design.

Step 2: Determine the amount of exhaust air

Evaluate whether exhaust airflow is sufficient to create recovery potential.

Step 3: Determine the humid heat state

Not only temperatures but also the psychrometric state of the two gas streams must be simultaneously viewed.

Step 4: Separate sensible and latent load

If latent load is large, ERV is often included in the comparison.

If your goal is primarily sensible recovery, HRV may be a reasonable option.

Step 5: Check exchanger

Rating:

  • Effectiveness.
  • Leakage.
  • Carryover.
  • Pressure drop.

Step 6: Fan and ductwork inspection

After adding ERV/HRV:

The actual airflow must still reach the design airflow.

It is not recommended to leave the condition of the system with heat recovery equipment but outdoor air is actually missing due to insufficient pressure head fan.

Step 7: Systemwide Energy Assessment

Compare:

Energy Recovered

With:

Fan + Motor + Control Energy

The ultimate goal is not to choose the exchanger with the highest effectiveness but rather:

Optimize HVAC Total Power

6 easy mistakes when designing ERV and HRV

Think ERV is always better than HRV

Sai.

ERVs only have the advantage if latent recovery is actually valuable to the system.

Just look at the temperature, ignore the humidity.

In hot and humid climates, this can misjudge ventilation load ratings.

Let's say that the ERV replaces the dehumidifier.

That's not true.

ERV only supports partial reduction of moisture load.

Select device by area

Area is not sufficient to determine airflow.

No pressure drop test

The consequences may be:

Fan lack of pressure head → Airflow decrease

No exhaust air rating

Exhaust air has contamination risk that cannot be defaulted to energy recovery.

ERV and HRV in ESG standard GREEN HVAC

Energy recovery is an important solution in energy-saving HVAC systems.

When selected correctly, an ERV or HRV can:

  • Reduce outdoor air handling load.
  • Reduce cooling load or heating load.
  • Reduces partial latent load with ERV.
  • Take advantage of exhaust air.
  • Reduce system - wide energy consumption.

However, an energy - efficient appliance does not automatically create a green HVAC system.

The effect must come from the whole chain:

Right design → Right selection → Right construction → Right TAB → Right control → Right operation