HVAC Air Balance: When Should It Be Checked And Calibrated?
Machine-translated from Vietnamese. Read the original in Vietnamese

What is air balancing HVAC? Signs, Causes and How to Adjust
Air balancing HVAC Air conditioning is the process of measuring and adjusting the air flow rate in the air conditioning ventilation system. This work helps AHU, fans, pipes, VAV Box and air outlets coordinate properly with design requirements.
A system can still run normally but the efficiency is not reached. Room near the subcooling fan, end-line heater room, air outlet strong place weak place or area often occluded with gas are common signs.
Instead of speeding up the fan or lowering the setting temperature, the business needs to check the actual flow rate and pressure to determine the right cause.
1. How is the wind system balanced?
The system is considered balanced when the flow rate at the branches and areas is consistent with the design parameters or actual use needs.
This does not mean that all air outlets must have the same flow rate. Each space will have different requirements:
- Meeting rooms need more outdoor air than small offices.
- The toilet area should be able to absorb odors.
- Technical departments need sufficient flow rate cooling equipment.
- The factory needs to supply wind and exhaust according to production characteristics.
- Cleanroom needs strict flow rate and differential pressure control.
Therefore, air balancing must be based on design documentation, room function and field measurement results.
2. How does air balancing loss affect?
Temperature between rooms is uneven
The area receiving lack of wind will be difficult to reach the set temperature. Meanwhile, the area receiving too much wind can get deep cold, causing discomfort to users.
Impaired air quality
Lack of outdoor air makes the room clogged and stuffy. Insufficient exhaust can cause odors from the toilet, kitchen or technical room to spread to other spaces.
Noise generation
Wind speeds too high or damper closing too much can create a squeak at the air outlet, VAV Box and pipeline.
Increase power consumption
When some rooms are not cool enough, the operator often speeds up the fan or lowers the temperature set. This way makes the device work more but does not necessarily solve the cause.
Operation device is unstable
Inappropriate pressure can cause the VAV Box to constantly open and close, the fan to run at high speeds, or the control system to frequently change parameters.
3. What signs to check air balancing HVAC
Enterprises should conduct inspection when the system appears one or more of the following phenomena:
- Cold front room, hot back.
- Air outlets in the same area have a markedly different flow rate.
- Some rooms do not reach temperatures despite continuous AHU operation.
- The crowds were quickly becoming overwhelming and stuffy.
- Odor or exhaust suction systems work poorly.
- Air outlet and VAV Box generate a hiss.
- High speed running fan but low cooling efficiency.
- The cost of electricity increases without much change in lifetime.
- VAV Box is max open but the area still lacks wind.
- After changing partition walls, premises or room function.
These signs should not be handled by sensation. Measuring flow rate and pressure will help to accurately identify abnormal positions.
4. Why does HVAC system lose air balancing?

Pipeline with too large pressure loss
Air duct is too small, the line is too long or there are many quails will increase pressure drop. Branches at the end of the line so often receive less wind.
Construction of improper records
Changes in hose size, flexible hose length, folded or misaligned position can all interfere with air flow.
Damper has not been calibrated.
Valves that close too much, are stuck or lack balancing valve causing flow rate between branches to be uncontrolled.
Air filter and dirty coil
Dust filtration increases pressure loss and reduces flow rate through the AHU or FCU. Dirty coils also impede airflow and reduce heat exchange capacity.
Pipeline leaks
Air loss at the joint, door or pipe damaged causing flow rate to the area of use is reduced.
Fan not enough pressure head
The fan can reach the nominal flow rate but not enough pressure to win the total pressure loss of the actual piping system.
VAV Box or BMS installed incorrectly
Sensor misalignment, actuator failure or inappropriate minimum and maximum flow rate settings can make each operation area unstable.
Usage has changed
The system is designed according to the original premises. When dividing more rooms, increasing the number of people or changing equipment, the flow rate demand also changes.
5. When should air balancing be done?
Before acceptance testing works
After the construction is completed, it is necessary to measure flow rate at the AHU, main route, each branch and air outlet to confirm the level of design response.
When the work is in use but the heat and cold are uneven
This is the time to measure before deciding to increase the capacity of equipment or replace the AHU, fan.
After renovation of the premises
Adding partitions, changing meeting rooms or increasing the density of people may make the old system no longer suitable.
After Replacement of Equipment
Replacing fans, AHUs, VAV Boxes, dampers or adjusting pipelines can all change the pressure and flow rate of the whole system.
When energy saving is needed
Air balancing data helps businesses know which areas are redundant or lack flow rate. From there, it is possible to adjust the fan speed, static pressure and BMS more reasonable.
6. HVAC air balancing test and calibration procedure

Step 1: Checking technical documents
Engineers determine the design flow rate of AHU, fan, main pipeline, branch by branch, air outlet, VAV Box, outdoor air and exhaust.
If there is no record, it is necessary to survey to establish assessment parameters in accordance with the current status.
Step 2: Check the device before measuring
Items to be inspected include:
- Filter and coil.
- Fan and straps.
- Variable-frequency drive.
- Damper.
- VAV Box.
- Sensors.
- BMS control status.
The system must operate stably so that the measurement results reflect the actual situation.
Step 3: Pipeline survey
The technician checks the pipe size, valve position, flexible hose, air outlet, leakage point and other potentially obstructive locations.
Step 4: Measure flow rate and pressure
Depending on the location, it is possible to use:
- Flow hood.
- Wind velocity meter.
- Pitot tube.
- Differential pressure meter.
- Static pressure gauge.
The result should be recorded along with the fan speed, valve opening and BMS status at the time of measurement.
Step 5: Analysis and correction
Based on the data obtained, the technician adjusts:
- Balancing valve.
- VAV Box.
- Fan speed.
- Variable-frequency drive.
- Static pressure.
- Control parameters.
Do not close or open an air outlet alone as this can change the flow rate of the entire line.
Step 6: Re-measure and report
After each adjustment, measure again to confirm the result.
The principle of implementation is:
Measure – Analyze – Adjust – Re-measure – Confirm.
The final report should show the design flow rate, actual flow rate, level of deviation, post-correction parameters and repair recommendations.
7. is air balancing TAB HVAC?
Air balancing is an important part of TAB HVAC.
TAB stands for Testing, Adjusting and Balancing, which means testing, calibrating and balancing the HVAC system.
Air balancing focuses on the air system. Meanwhile, full TAB can include:
- Chilled-water system.
- pump flow rate.
- Differential pressure of water pipes.
- AHU and FCU parameters.
- Ability to coordinate between equipment and control systems.
8. Does air balancing help reduce electricity bills?
Air balancing can support power saving if the system is distributing unreasonable flow rate.
When insufficient airflow areas are handled properly, the business can limit fan acceleration or reduce excessive setting temperature.
However, the actual effect depends on:
- Fan and AHU status.
- Clean level of filtration and coil.
- Airtightness of pipeline.
- Install BMS.
- Time of operation.
- Practical uses.
Therefore, it is not recommended to commit a fixed saving rate when not yet surveyed and measured.
9. HVAC air balancing solution at HRT
HRT evaluates the equipment, pipelines and control systems in sync before making a treatment plan.
The scope of inspection may include:
- AHU, FCU and fan.
- Pipe glands and fittings.
- Balancing valve and air outlet.
- VAV Box.
- Outdoor air, return air and exhaust.
- Air filter and coil.
- Static pressure.
- Variable-frequency drive, sensor and BMS.
If the cause comes from dirty filtration, it should be cleaned before calibration. If the pipe leaks or the flexible pipe is folded, it should be repaired the pipeline. If the equipment is not enough pressure head, it should be re-evaluated the responsiveness of the fan.
HRT aims to identify the right cause, correct data and help the operation system more stable and economical.
See more:
Industrial Air Conditioner VRV
Industrial Air Conditioner Chiller
VRF Industrial Air Conditioner
Conclusion
Air balancing HVAC not only the air outlet adjustment but also the whole system evaluation process from fan, AHU, pipeline, damper to VAV Box and BMS.
The correct measurement helps overcome the uneven heat and cold, weak wind, noise, airflow and electrical operation.
Enterprises should check air balancing after construction, after renovation or as soon as the system appears abnormal signs.