Sizing VRV ductwork: why horsepower alone is not enough

Machine-translated from Vietnamese. Read the original in Vietnamese

Select VRV air duct size: Don't start with HP

CEO Đoàn Văn Hoàng – HRT share how to choose the size of air duct VRV based on flow rate, velocity, pressure drop and ESP of the right indoor unit. The goal is to bring the right amount of wind to the right area, stable operation and can be verified by actual measurement.

Select VRV air duct size: Don't start with HP

Select size air duct VRV

Imagine a situation at work.

Ceiling-concealed indoor unit VRV was working. air outlet near the blower was quite strong, but the end of the line had a feeling of lack of wind. The engineering team proposed speeding up the fan. Another opinion suggested that it was necessary to increase the pipe size.

Before making any adjustments, I want the project team to answer a simple question:

The system is missing flow rate because of small pipes, because of large pressure loss, because of improper calibration or because the fan of the indoor unit has not been installed in accordance with the actual pipe network?

That's how I approached it. choose size air duct VRV.

I don't want to start from an HP checklist. I want to start with the amount of air that needs to be delivered to each area, then check if the indoor unit can afford to get that air through the entire pipe network.

The original HRT article also identified four important data groups including airflow rate, velocity, pressure drop and external static pressure of the indoor unit. cooling capacity is not the only basis for inferring pipe size.

Starting from where the user receives air

 VRV air duct size

When browsing the air duct system for indoor unit VRV, I suggest that the engineer do not look at the body first.

Look at the uses.

What area needs how much wind? Which feeder serves that area? From the indoor unit to the air outlet must go through how many pipe sections, how many quads, branches and accessories?

Once the answer is clear, the pipe size has a basis.

Flow rate is the task assigned.

Airflow rate of indoor units is usually announced by the manufacturer according to each model and fan mode. Two indoor units with close cooling capacity may still differ in flow rate and fan characteristics. Therefore, it is not recommended to take HP or kW refrigeration and then apply a fixed pipe size.

At the design step, I want the distribution board to clearly show:

How much indoor unit provides total flow rate?

How much does each area need?

How much is each branch given?

Does the sum of branches match the expected operation mode of the device?

Without these data, the debate over whether 300×200 or 350×200 mm tubes are available is premature.

Crossing is a first step, not the end result.

The basic relationship between flow rate, velocity and cross section can be written:

A = Q / v

Where:

  • A is the airflow cross section.

  • Q is flow rate.

  • v is the average velocity.

The formula gives us the initial theoretical size.

But at the site, I didn't want the project team to stop at this calculation.

The same cross section, the choice of shape, double edge ratio, line length, number of accessories and branching will change the pressure loss of the system. The original article also noted that after determining the cross section still need to check the machining size, velocity and pressure drop of the whole line.

There is no one speed for every pipe segment

If selecting small cross section, the velocity increases. That can increase pressure drop and noise.

If excessive cross section is increased, ceiling space and material costs may increase.

So I don't use the “big tube is better" or “small is cheaper" thinking.

The velocity should be selected according to route location, noise requirements, flow rate and system conditions. The original article also does not give a single velocity for all feed and return lines, but requires consideration on a case-by-case basis.

Each size has to answer why it fits in that pipe.

After cross section, ask the fan how much pressure loss it wins

This is the part I want the validator to pay special attention to.

Indoor unit connecting air duct not only needs to create flow rate. The fan also has to bring that amount of air through the pressure loss of the pipe network.

Pressure loss is not just on the straight pipe section.

It also appears at quail, numbness, branch turns, damper, filter, acute mouth, antrum and other accessories. The longer the gland and the more directional changes, the greater the total loss can be.

Find the most disadvantageous route

I asked the design team to point out the most detrimental total pressure loss from the indoor unit to the distribution point.

At that route, it should be clarified:

What is the design flow rate?

What is the frictional loss along the way?

How much additional pressure loss does the accessory cause?

How much does air outlet and adjustment valve contribute?

Is the total pressure loss ultimately within the fan's capacity?

If these questions are not answered, indoor units should not be considered capable of serving pipe networks.

ESP must be read in accordance with the model indoor unit

VRV

External Static Pressure – ESP, or external static pressure, is the important data when designing air duct for indoor unit connecting pipe.

I don't want an ESP value to be taken from one model and applied to another.

Daikin, for example, announced the FXSQ-A series as a ceiling-concealed medium-voltage indoor unit, with ESP capability up to 150 Pa in this product; the document also allows ESP adjustment to optimize flow rate levels. This is a specific line/model characteristic, not the default number for every VRV indoor unit.

Daikin's service documentation also shows that some FXMQ models have different ESP setting levels according to their model. This further indicates that it is necessary to look up the correct equipment documentation rather than using a common parameter.

Do not confuse “ESP max” with “just take it as well”

If the catalogue allows a high ESP level, that does not mean the design should create a pipe network with pressure loss close to the limit if it is not necessary.

I want the pipeline to be reasonably organized from the beginning: limit unnecessary diversions, clear branch layout and select the right cross section.

Fan capability is the resource for the system to meet the requirement, not the reason to accept an unreasonable pipeline.

A dash on the drawing board could change the story at the scene.

At the design stage, a redirect can look very simple.

Until it coordinates with the structure, electricity, sprinklers and other MEP lines, the pipe may have to be redirected several times.

That's when I asked the HVAC team to reopen the affected computation.

Don't assume that the same section of the tube will always be the same.

Each stroke, branch, retractor or sectional extension can affect local loss. The original article HRT also warns glands with too many strokes and branches that turn can increase pressure loss and affect wind distribution.

Change Lines Must Pull Follow Recheck

If the scene is forced to change pipelines, I suggest that the record show:

Which passage changed?

Reasons for change.

Does the adverse route change?

Does the total pressure loss need to be recalculated?

Whether or not you need to do the fan settings or calibration again.

This last point is particularly important.

Daikin instructs FXSQ-A that if ventilation lines change, automatic flow rate adjustments should be made again according to the applicable procedure. The document also requires adjustment of damper to flow rates at entrances and exits in accordance with the flow rate design.

A change on the windway should not end with correcting the drawing. It should end with confirming the system still works properly.

Equal Friction or Static Regain is not the name to be written in the explanation

The original article mentioned two commonly used methods are Equal Friction and... Static Regain.

I wanted the design team to understand the purpose of the method chosen instead of just naming it.

With Equal Friction, a friction loss rate is used as the basis for determining the size of pipe segments according to the flow rate. The velocity, fittings and the ability to balance between branches must then be checked.

Static Regain aims to use velocity reduction to recover some of the static pressure as flow rate decreases along the line.

There is no method that will help bypass the actual test of the pipe network.

If the system has many branches, long segments and different wind distribution requirements, I want the designer to explain why the method of choice is suitable for the building configuration.

Rectangular, round or flexible pipes must serve the same objective

air duct VRV

In low ceilings, rectangular tubes often facilitate pitch coordination.

Round tubes have geometries favorable for airflow but set their own conditions for space and fittings.

Flexible hoses are useful at some air outlet connections, but length, deflection and flexure directly affect pressure loss. The original article recommended not to use flexible hoses arbitrarily in place of the main route.

From a management perspective, I do not approve the spool shape because “it is easier to construct".

I want the alternative to proving three things at once:

We can walk in architectural space.

Meet the flow rate and pressure loss.

Can be applied, maintained and calibrated in practice.

Do not force the tube too flat just to overcome a conflict

With rectangular pipe, when keeping the same area but changing the two-side ratio sharply, the hydraulic characteristics and machining conditions are no longer the same.

If the high - pitched conflict forces the tube to be very wide and very low, I suggest checking the alternative instead of just resizing the geometry to fit.

Sometimes the right solution is not to squeeze a smaller tube, but to adjust the gland or re-coordinate the pitch with another system.

When lack of wind, do not rush to increase the tube size

Suppose that after construction, an air outlet at the end of the measurement line does not reach the flow rate.

I don't want to make the first decision to remove the tube and replace it with a larger size.

Let's check the cause in sequence.

Where's damper?

Is the filter clean?

Is the flexible tube folded or sag?

Is the construction route in the right dossier?

Is ESP installation of indoor unit suitable?

Flow rate of near branches are calibrated?

The original article also noted that low flow rates can come from filters, damper, accessories, pressure loss and fan mode; so it is not recommended to increase the size only when not yet tested the whole system.

This is how I want the project team to handle the problem: determine the cause first, decide to intervene later.

Pipeline is completed when flow rate at the place of use is confirmed

A nice system on the drawing is not the end result.

After construction, it is necessary to check the actual size and gland, quality of joints, mounts, insulation and accessibility. Then comes the operation measurement.

I am particularly interested in the flow rate at air outlet.

Do not acceptance testing only by “there is wind”

When measuring, I want to know which air outlet is being tested, how much design flow rate and how much actual result.

If one branch is not reached, re-measure it.

If weighing one branch significantly changes the other, the distribution network should be evaluated instead of continuing to adjust each valve sensorily.

Daikin instructs FXSQ-A that when multiple doors are available, dampers should be adjusted to allow flow rates for each door to match the design.

The final measurement should become part of the handover record so that the operator knows the system status at the time of receipt.

Air duct is not acceptance testing by the size on the gauge. It needs to be acceptance testing by its ability to get the right amount of wind to the right place.

CEO view Đoàn Văn Hoàng: I didn't choose a pipe size, I chose a verifiable path.

When I look at a VRV air duct, I want the designer to explain the whole story.

Where does the flow rate come from?

Why did this segment choose that velocity?

Where is the disadvantageous line located?

What is the total pressure loss?

Does ESP of the right model respond?

How will the measurement and calibration be done after construction?

If these questions are answered clearly, the size number on the drawing makes sense.

I don't want the construction team to choose the pipe according to HP experience. I also don't want an ESP value on the catalog to be a reason to ignore the linear optimization.

That's how I apply the spirit True – Clear – Dedicated.

Understand correctly flow rate and duties of each area.
Clearly about the velocity, pressure loss and fan capability.
Dedicated measure again until the actual wind meets the agreed plan.

To me, how to choose VRV air duct size does not start with the question “how much is enough tube”

It begins with the question:

At the end of this pipeline, how much wind do we need to deliver — and is the entire system capable of getting that wind to where it needs to be?

Exchange air duct VRV with HRT

When it is necessary to review the system, the project owner should prepare the model indoor unit, the use of premises, flow rate design, wind line drawings and information on the location that is reflected.

With the work already in operation, data measured flow rate at air outlet and indoor unit settings will help localize problems faster.

From that data, HRT can together with the project owner review the pipeline, pressure drop, ESP and calibration options before deciding to change equipment or renovate the pipeline.

CEO Đoàn Văn Hoàng | HRT