What is a Chiller System? Structure, Principles and Practical Applications

Machine-translated from Vietnamese. Read the original in Vietnamese

What Is Chiller System? Structure, Principles And Practical Application

Chiller system is a central cooling solution that uses cold water to supply AHUs, FCUs, PAUs or technological equipment. Together with HRT learn the structure, principles, applications, types of chillers and important factors when designing the system.

What is Chiller System?

Chiller System is a form of central cooling system, in which the Chiller creates cold water and then distributes cold water through pipeline systems to heat exchangers such as AHU, FCU, PAU or coil technology.

Simply put:

Chiller generates cold water → Pump transports cold water → AHU/FCU uses cold water → Air is cooled → Water returns to the Chiller.

Different from VRV / VRF air conditioner bring refrigerant directly to the indoor unit, Chiller system uses water as refrigerant transport intermediates.

This characteristic helps the Chiller to be suitable for many large-scale projects or centralized cooling load such as:

  • Factory, industrial park.
  • The mall.
  • Office building.
  • Hotel, resort.
  • Hospital.
  • Data center.
  • The production line needs cold water technology.

A Chiller System Doesn't Just Have Chiller Machines

This is a very important point.

Many people refer to Chiller and only think of the cold water generator. But in reality, the operation efficiency depends on the Whole HVAC System Around Chiller.

A typical system may include:

Chiller → chilled-water pump → Line chilled-water pipe → Valve → AHU/FCU/PAU → Control → BMS.

If using water-cooled chiller will have additional:

Water condenser pump → Cooling pipeline → Cooling Tower → Water treatment system.

In addition, the following must be taken into account:

Electrodynamics, electrical control, sensors, gauges, insulation, condensate drainage, air duct, air outlet, TAB system and commissioning.

So:

The performance of a chiller system is not equal to the specific performance of the chiller.

For good operation system must optimize synchronization machine – pump – pipeline – terminal – control.


4 Main Parts Inside Chiller

For chiller using vapor compression refrigeration cycle, it is possible to understand the machine through 4 core components.

Compressor – Compressor

Compressor sucks refrigerant in low pressure state and compressor to high pressure.

This is an important part of the refrigerant cycle.

Common compressor types include:

  • Scroll.
  • Screw – screw.
  • Centrifugal – centrifuge.

The choice should not be based solely on the maximum power, but should also consider:

Load by piece – performance – noise level – maintenance capability – operation time – life-cycle cost.

Evaporator – Evaporator

Evaporator is where the water is cooling.

The return water from the AHU/FCU passes through the evaporator and transfers heat to the refrigerant.

Results:

Hot water returns → Chiller → chilled-water supply back to the system.

Condenser – Condenser

Condenser is responsible for releasing heat into the environment.

Depending on the way of heat discharge, Chiller is generally divided into:

Air-Cooled Chiller – air-cooled chiller.

and...

Water-Cooled Chiller – water-cooled chiller.

Expansion valve

Expansion valve reduces the fluid pressure before the fluid returns to the evaporator.

The cycle then continues to repeat.


Chiller principle can be understood through 3 cycles

Instead of just looking at the Chiller, it's easier to understand if you divide the whole system into three loops.

Round 1 – refrigerant

Basic Cycle:

Compressor → Condenser → expansion valve → Evaporator → compressor.

Refrigerant takes the heat from the water at the evaporator and transfers that heat to the condenser for discharge.


Round 2 – CHW Cold Water

This is the ring directly provides cold energy for the building:

Chiller → CHW pump → AHU/FCU/PAU → Water return → Chiller.

At coil of AHU or FCU:

Cold water absorbs heat from the air.

The air after coil is cooled down and brought into the room or production area.


Round 3 – condenser water

This ring is usually available in Water-Cooled Chiller:

Condenser → Water condenser pump → Cooling Tower → Condenser.

Cooling Tower helps to transfer the heat that the system collects to the environment.


What do AHU, FCU and PAU do in Chiller system?

Chiller produces cold water but do not directly supply cold air to the room.

The air handling work mainly belongs to terminal.

AHU – Air Handling Unit

AHUs typically serve areas with high airflow rates.

Can Integrate:

  • Coil cold water.
  • Air purification.
  • Outdoor air.
  • Windswept.
  • Dehumidify.
  • Heat or reheat.
  • Special filter grades.

AHUs usually appear at:

Factory, commercial center, hotel, hospital, cleanroom and large building.

FCU – Fan Coil Unit

FCUs are usually smaller than AHUs.

Equipment suitable for handling each room or each zone.

HRT commonly used FCU Concealed Ceiling Combination:

Chilled-water pipe + condensate + air duct + air outlet + thermostat/controller.

PAU – Primary Air Handling Unit

PAU usually handles outdoor air before putting into the building.

In projects requiring humidity control or large amounts of outdoor air, PAU is a very important component.


How are air-cooled chiller and water-cooled different?

These two configurations both produce cold water but different heat discharge.

Criteria Air-cooled chiller Water-cooled chiller
Heat exhaust method Air conditioner Water
Cooling Tower No Often there are
Water Condenser Pump No Yes
Auxiliary system Simpler More complicated
Water Treatment Less than Important
Spaces Need a well-ventilated area Need machine room + cooling tower
Operation Simpler Requires more device management
Applications Many medium/large projects Large loading works, centralized operation

Don't assume that one is better than the other.

Need to compare by:

Cooling load + number of hours of operation + climate conditions + water source + technical area + noise + electricity + maintenance + life-cycle cost.


ΔT – small parameter but great effect on the Chiller

One of the parameters to monitor regularly is ΔT cold water.

Formula:

ΔT = T water return – T water supply

About thermal balance:

Q = ṁ × Cp × ΔT

Where:

  • Q: cooling load.
  • ṁ: water volume flow rate.
  • Cp: specific heat capacity.
  • ΔT: temperature difference.

This shows that cooling load is not only related to water temperature but also directly related to water flow rate.

If ΔT is abnormally low:

The system may have to push a larger flow rate to meet the load.

From it can cause:

Increase flow rate → increase pump capacity → affect hydraulic balance → reduce system extraction capacity.

So it is necessary to control simultaneously:

Flow + ΔP + ΔT + actual load.


How many degrees does chiller water normally have?

In many comfortable air conditioning systems, the reference configuration may be encountered:

Water supply is around 7°C.

The water should be around 12°C.

Corresponding:

ΔT ≈ 5 K.

However, this is not a requirement for every project.

The design temperature should depend on:

  • Temperature – humidity conditions.
  • Coil AHU/FCU.
  • Cooling load.
  • Production technology.
  • Request dehumidification.
  • Chiller of choice.
  • Energy saving strategy.

Therefore, it is not recommended to apply a set of parameters to every building.


What type of pump does the Chiller system usually use?

Customized hydraulic scale and design, there are various configurations.

Primary – Secondary

The system is divided into:

Primary Ring Walk through Chiller.

and...

Secondary round distribute water to the load.

This is the configuration that has been commonly used in many chilled-water central systems.

Variable Primary Flow

The system can change the water flow rate through the distribution network by variable-frequency drive and control system.

The potential advantage is reduced pump power as the load decreases.

However, it must ensure:

  • Minimum flow rate through Chiller.
  • Manufacturer's operating conditions.
  • Differential pressure system.
  • Control sequence.
  • Control valve and bypass fitting.

Hence:

It is not only install variable-frequency drive for pumps that the system has optimized.


Where is the chiller applied?

Factory and Industrial Zone

Chiller can serve both:

Comfortable air conditioning and... cooling technology.

Some applications:

  • Cooling the line.
  • Cooling machinery.
  • Control the temperature of production area.
  • Provide cold water for technological equipment.
  • Factory air conditioner.

Office Buildings

Buildings with large cooling loads can organize the system in multiple zones.

Chiller combined AHU / FCU helps to concentrate the refrigeration source but still divide the load by each area.


Business Center

Commercial centers usually have:

Volatility, high lighting load, multiple functional areas and large outdoor air requirements.

The system may include:

Chiller + AHU + FCU + PAU + BMS + outdoor air + exhaust.


Hotels & Resorts

Chiller can serve:

  • Resting room.
  • Lobby.
  • The restaurant.
  • Ballroom.
  • The conference area.
  • Service area.

In some projects, the combination of Chiller and VRV/VRF can be used to optimize each area.


Hospitals

In addition to cooling load, hospital HVAC is also related to:

Outdoor air – differential pressure – filter – humidity – infection control.

Therefore, the design can not be based solely on conventional cooling loads.


Data Center

Continuous heat-generating IT systems can use chilled-water systems as part of their cooling solution.

Important requirements typically include:

Reliability – redundancy – 24/7 operation – precise temperature control.


When should you consider using a chiller?

There is no single threshold area to decide.

The selection should be considered simultaneously:

Cooling load → profile load → time operation → power → temperature/humidity → outdoor air → power supply → water supply → technical space → noise → maintenance → redundancy → scalability.

An important principle:

Do not choose Chiller only by floor area.

Two buildings with the same area may have completely different cooling loads.


7 Common Errors When Deploying Chiller Systems

Chiller System

1. Choose Chiller by area instead of cooling load

This is the error from the first step.

Selecting a lack of power may cause the system to not respond to load.

Too much residual selection may cause the device to not be optimally operational.


2. Only care Chiller machine performance

The whole system also has:

Pump + cooling tower + AHU/FCU + fan + controller.

If your chiller is high - efficiency but the pump or control system is not reasonable, the total power may still be high.


3. Hydraulic design is not good

A system may appear:

  • Water shortage in the distal branch.
  • Differential pressure is too high in the proximal branch.
  • Difficulty balancing.
  • The control valve is unstable.

4. Uncontrolled ΔT

Low ΔT can increase the water flow rate required and affect system extraction capacity.


5. Skip water treatment

Especially for water-cooled chiller.

Possible problems include:

Scaling – fouling – corrosion – reduced heat transfer efficiency.


6. Not leaving enough maintenance space

The machine can fit in place.

But check:

Space remove motor – tube – heat exchanger – filter – valve – pump – electric panel.

Lack of maintenance can cause costly repairs in the future.


7. TAB and Commissioning are incomplete

After construction, it is necessary to measure and verify the actuality:

Water flow rate – airflow rate – temperature – pressure – ΔP – ΔT – control sequence – interlock.

An HVAC system is only truly complete when operation in accordance with the design and requirements of use.


Process of deploying Chiller system at HRT

Chiller System

HRT controls projects in series:

Survey → Load analysis → Design → Equipment selection → Construction → TAB & Commissioning → acceptance testing → Handover → maintenance & optimization.

Step 1 – Survey

Collect information about:

Function, architecture, structure, thermal load, outdoor air, electricity, water, machine room, cooling tower and operation conditions.


Step 2 – Load Analysis and Design

Calculation:

Cooling load → Chiller → AHU/FCU/PAU → Pump → Pipeline → Valve → Sensor → Control.

Also evaluate the requirements for redundancy and expansion.


Step 3 – Select your device

The equipment is selected based on actual operation conditions instead of just based on the nominal power.

Need to see:

  • Full-load.
  • Part-load.
  • Noise level.
  • The size.
  • Power supply.
  • Flow rate.
  • Pressure.
  • Maintenance capability.

Step 4 – Synchronous construction

HRT Synchronous Control:

Chiller – AHU – FCU – pump – cold water line – condenser water line – valve – meter – thermal insulation – air duct – air outlet – electrical dynamics – electrical control.


Step 5 – TAB & Commissioning

Measurement and calibration:

Flow – ΔP – ΔT – airflow rate – temperature – pressure – sequence operation – interlock.


Step 6 – acceptance testing and handover

Testing:

  • Equipment.
  • Water system.
  • The wind system.
  • Controls.
  • Alarm.
  • Interlock.
  • As-built documentation.
  • Operation manual.

Step 7 – maintenance and optimization

After system operation, the data such as:

ΔT, Chiller load, pump capacity, cooling tower, water temperature, differential pressure and equipment running time

can be further monitored to detect suboptimal points.


What is the difference between a chiller and a VRV/VRF?

The fundamental difference lies in the way cold energy is transmitted.

Chiller

Use:

Cold water → AHU/FCU → Air conditioning space.

Advantages when needed:

  • Big capacity.
  • Big AHU.
  • Cold water technology.
  • Concentrate air treatment.
  • Chiller plant center.

VRV/VRF

Use:

Refrigerant → indoor unit in the room.

Usually advantageous with:

  • Small partition.
  • Independent control.
  • The office.
  • The villa.
  • The hotel.
  • Works with distributed load.

Do not compare with simple questions:

“Which is better,iller or VRV?"

The question is more correct:

Which solution is better suited to the load, performance and life cycle of the building?


An efficient chiller system needs to optimize the whole system

When evaluating the efficiency of a Chiller, HRT does not just look at the air conditioner.

It is necessary to consider simultaneously:

Chiller + Pumps + Cooling Tower + AHU/FCU + Hydronic System + Controls + BMS.

For example:

A very high efficiency Chiller but pump running 100% continuously while low load can still make the total power of the system high.

Or:

The AHU lacks water flow rate, causing the valve to open at full capacity, pumping up speed but the room still fails to reach temperature.

Therefore the important philosophy is:

System optimization, not device optimization.


Frequently Asked Questions About Chiller System

What is Chiller?

Chillers are devices that produce cold water or cold solutions for air conditioning or industrial cooling.

Does the chiller directly blow cold air into the room?

No, no, no.

Chillers generate cold water. An AHU or FCU uses that cold water to process air.

Does water-cooled chiller need cooling tower?

In common configuration, yes.

Cooling tower is used to discharge heat from the condenser water ring into the environment.

Are AHU and FCU Chillers?

No, no, no.

This is the terminal that uses cold water supplied by Chiller.

What unit does the chiller use?

The capacity can be expressed as:

kW Refrigerant or RT.

In priority HRT design SI system and RT conversion when need to reconcile equipment.

Is the chiller more electrically efficient than VRV?

Can't conclude in general.

Must compare:

Load → operation time → partial performance → pump → cooling tower → AHU/FCU → control → climate condition.

Should I choose Chiller by area?

No, no, no.

Area is just an initial data set.

Cooling load should be calculated based on:

Structure → glass → sunshine direction → people → equipment → lighting → outdoor air → technology loading → life time.


HRT – HVAC solution and Chiller system for buildings

HRT offers HVAC solution in series:

Consulting → Design → Supply → Construction → acceptance testing → maintenance → Optimization – renovation.

The deployed HRT systems include:

Water Chiller – AHU – FCU – PAU – VRV/VRF – Packaged/Rooftop – HRV/ERV – BMS – outdoor air system – exhaust – pipeline – air duct – air outlet and control.

The goal of HRT is not just to get the equipment.

More importantly, the system must:

Right load – right flow rate – right ΔT – right control – easy maintenance – stable operation – optimal energy.

HRT – Green Breath for All Buildings

Right From the Start – Clear To the End – Green Sustainable.


Conclusion

Chiller System is a central cooling solution capable of serving from comfortable air conditioning to industrial cooling needs.

A complete system not only includes Chiller but also the coordination between:

Chiller → Pump → Pipeline → AHU/FCU/PAU → Cooling Tower → Controller → BMS → TAB & Commissioning.

The effectiveness of the system depends on whether all of those components are designed and operated in sync.