WHAT IS A STAIRS BOOSTING SYSTEM? STRUCTURE, PRINCIPLES AND DESIGN NOTES

Machine-translated from Vietnamese. Read the original in Vietnamese

WHAT IS THE stairwell pressurization SYSTEM? STRUCTURE, PRINCIPLE AND DESIGN NOTES

Stairwell pressurization system helps create positive differential pressure, limit smoke ingress and support the escape route when fire occurs. Learn the structure, operating principles, how to choose fans and important notes when designing, operating.

1. What is stairwell pressurization system?

Stairwell pressurization system is a smoke control solution by feeding air into the ladder chamber to create higher pressure relative to the corridor or adjacent area.

The main goal is to create a trend in airflow from the stairwell outwards, thereby limiting smoke from entering the evacuation route when fire occurs. This is a smoke control system, not a direct fire extinguishing system.

Points to be especially noted: The bigger the fan, the safer it may not be.. If differential pressure is too high, the force on the door increases and may make it difficult to open the evacuation door.


2. Why do stairs need to be turbocharged?

The stairwell is one of the most important vertical routes when evacuating.

When smoke enters the stairs, the visibility and navigation of the user may be affected. At the same time, the staircase is a vertical shaft connecting multiple floors, so the chimney effect, temperature and pressure differences can cause smoke to spread along the height of the building.

Booster system helps:

  • Reduce smoke in the stairwell.
  • Direct airflow from stairs to corridors when doors open.
  • Supporting the maintenance of evacuation routes.
  • Limit stairs to vertical pathways of smoke.
  • Coordinate with smoke extraction system and other fire safety systems.

However, the effect depends on airtightness of the stairwell, door status, fan, smoke extraction system, wind condition and control way system.


3. The working principle of stairwell pressurization system

stairwell pressurization system

The principle can be understood according to 6 Main Steps:

Step 1 – Receive fire alarm signal

When the signal appears according to the control logic of the work, the control cabinet sends the command to start the supercharging system.

Depending on the cause – effect matrix, the system can simultaneously:

  • Start the fan.
  • Open damper.
  • Change variable-frequency drive status.
  • Start a backup fan.
  • Coordinate with smoke extraction system.

Step 2 – Outdoor air intake fan

Exhaust fan clean air from outdoor and put into system.

The location of the inlet must be arranged appropriately to limit the risk of re-sucking smoke from the exhaust or other sources of pollution.

Step 3 – Air is supplied to the stairwell

Air passes through the shaft or ductwork and is fed into the staircase at one or more locations.

System can use:

Grade of one point: simpler construction.

Multiple points: support gas distribution in multi-level or multi-height zones.

Each option must be calculated based on the actual characteristics of the work.

Step 4 – Form differential pressure

When the air inlet flow rate is greater than the air outlet through the leakage, the pressure in the ladder chamber increases.

Air tends to leak:

Ladder chamber → door slot → corridor

instead of letting the smoke move in the opposite direction.

Step 5 – Reaction system when door open

When the exit door is open, the air escape area increases sharply.

Differential pressure in the ladder chamber will decrease and the fan needs to provide sufficient flow rate to maintain the outward airflow direction.

Some systems use:

  • Variable-frequency drive.
  • Multi-level fans.
  • Differential pressure sensor.
  • Pressure outlet.
  • Logic controls the door state.

Step 6 – Overvoltage Control

When the doors are closed, pressure can rise.

Pressure outlet or fan speed control system will help limit overpressure, avoiding the disaster exit door difficult to open.

Principle diagram:

Fire alarm → pressurization fan operation → Outdoor air supply → Elevator chamber booster → Corridor outflow gas flow → Coordinated smoke extraction system


4. Structure of stairwell pressurization system

Structure

A complete system is usually composed of many items that work together.

Pressurization fan

A fan is a device that creates flow rate and pressure for the system.

When choosing to check:

  • Flow rate.
  • Total pressure.
  • Performance curve fan.
  • Performance.
  • Engine power.
  • Noise and vibration.
  • Control mode.
  • Backup plan if required by the application.

Do not choose a fan based solely on motor capacity or stair area. The actual working point must consider both flow rate and total pressure loss system.

Outdoor Air Intake Door

This is what provides air for the fan.

When arranging should be noted:

  • Avoid sources of smoke.
  • Avoid smoke vents.
  • Limit rainfall.
  • Limit dust and pollution sources.
  • Calculate pressure loss through louver and protective net.

Shaft or air duct booster

Bring air from the fan to the supply sites.

Need Control:

  • The size.
  • Speed.
  • Pressure drop.
  • Airtightness.
  • Hanging.
  • Requirements for materials and refractories according to applicable profiles.

A high air duct leak may cause the fan to run at full capacity but the pressure at the stairs is still below.

Mouth wind supply

The acute mouth directly affects the distribution of flow rate between layers.

For multi-point supply system, it should be balanced to avoid the situation that the near floor of the fan receives too much wind while the far floor lacks flow rate.

Damper

Damper can be used to:

  • Adjust the flow rate.
  • Close/open by zone.
  • Isolate the branch.
  • Coordinate with the state of fire.

It is necessary to determine the right type of damper according to the function, no damper should be considered every fireproof valve or smoke valve.

Pressure outlet

Pressure outlets help limit differential pressure that is too high when stair doors are closed.

If opened too early → the system may not be pressurized enough.

If open too late → the pressure can be too high and make it difficult to open the door.

Differential pressure sensor

The sensor measures the pressure difference between the ladder chamber and the reference area.

Signals can be used to:

  • Supervise.
  • Warn.
  • Variable-frequency drive control.
  • Adjust the fan speed.

For high-rise buildings, only one measurement point may not accurately reflect the entire height of stairs.

Variable-frequency drive – VFD

Variable-frequency drive allows adjustment of fan speed.

For example:

Door closed → deceleration to limit overpressure.

Door open → acceleration to compensate flow rate.

However, variable-frequency drives are not configured by default for all turbochargers; the control scheme must be appropriate for each project.


5. The two most important states to check

When the stairs door is closed

The goal is to maintain differential pressure so that air flow tends to go from the staircase outward.

If the pressure is too low → the ability to limit smoke decreases.

If the pressure is too high → the door may be difficult to open.

When the stairs door opens

When the door is open, the air escape area increases greatly.

Measurement of differential pressure is not enough; depending on the application profile, it is also necessary to evaluate flow rate or velocity of gas flow through the open door.

This is why it is not advisable to acceptance testing the system by only turning on the fan and then measuring the pressure when all doors are closed.


6. How to choose pressurization fan stairs

A common mistake is:

“The area of the staircase is how much to choose the fan CMH”

This choice is lacking in grounds.

Fan flow rate depends on many factors:

Total air leakage

Includes:

  • The doorway.
  • John.
  • Perforation.
  • Shaft.
  • Architectural gaps.

Number of Doors Open

One door open and multiple doors open create completely different flow rate demands.

Building height

The higher the construction, the more the effect of loss and chimney effect should be considered.

Total pressure loss system

Loss should be calculated at:

  • Louver.
  • Air duct.
  • Get lost.
  • Damper.
  • Air outlet.
  • Other accessories.

So the fan needs to be selected according to flow rate + total pressure at working point, not just according to the nominal flow rate.


7. How different is stairwell pressurization and smoke extraction?

The two systems have different functions but can interact directly.

Stairwell pressurization:
Insert air into the area to be protected to create relative positive pressure.

Smoke extraction:
Remove smoke and air from the burned area, creating a low pressure trend in the suction area.

Booster system do not replace smoke extraction system, and the smoke extraction system also does not default to protect stairs.

When both systems are in operation, the pressure of the corridor changes so differential pressure through the staircase door also changes. Therefore, it is necessary to evaluate the two systems in the same operation scenario.


8. Factors that cause the pressure booster system to fail

The stairwell is too exposed.

Door seals, damaged gaskets, or untreated air inlets cause a lot of air loss.

Fan not enough total pressure

The fan reaches free flow rate but when it is applied to the pipeline, it does not exceed the total pressure loss.

Air duct leaked

A portion of the flow rate is lost before reaching the ladder chamber.

Badly functioning Damper

The fan runs but the damper is not properly opened, causing the actual flow rate to decrease.

Sensor misplaced

Non-representative signals can cause variable-frequency drive control to be wrong.

Badly calibrated pressure outlet

Opening it too early or too late can cause the system to malfunction.

Uncoordinated smoke extraction system

Over-closed corridors or variable corridor pressures can significantly affect air flow through the door.


9. Common mistakes when designing and operating

Select a fan by the size of the stairs.

Assume the fan is as big as possible.

Only check when the doors are closed.

Do not measure at unfavorable levels.

Do not test the opening force.

Do not calculate the actual amount of leakage.

Ignore differential pressure due to chimney effect.

Unbalanced oral acute.

Set differential pressure sensor at non-representative position.

Do not test for smoke extraction.

Change doors, walls or architecture but do not recheck the booster system.

These problems can lead to the the fan is still running but the system does not perform its function of smoke control.


10. Stairwell pressurization system test procedure

Processes

Step 1 – Review your profile

Determine:

  • The area is secure.
  • Number of fans.
  • Zone.
  • Flow rate.
  • Total pressure.
  • Logic controls.
  • Door status.
  • Related smoke extraction systems.

Step 2 – Check the status quo

Testing:

  • Fan.
  • Air duct.
  • Damper.
  • Acute mouth.
  • Pressure outlet.
  • Fire door.
  • Tay co.
  • John.
  • Sensors.

Step 3 – Interlocking Test

Signal simulation by script to confirm:

Fire alarm → damper → fan → variable-frequency drive → smoke extraction → status feedback

Step 4 – Measure when the door is closed

Measure differential pressure at the locations and floors to be tested.

Step 5 – Check when the door is open

Evaluate differential pressure, gas flow and related requirements according to applicable records.

Step 6 – Calibration and acceptance testing

Adjustable:

  • Fan speed.
  • Damper.
  • Pressure outlet.
  • Setpoint sensors.
  • Logic controls.

Working Fan running does not mean the system is satisfactory; should be measured at operational states and at disadvantageous levels.


11. Regulations to be noted

Determining which works must be arranged turbocharger, protection scope and design criteria should not be based on an overview article.

For each project, it is necessary to compare:

  • Design documentation.
  • Ladder type.
  • Functional.
  • The height of the work.
  • Organize an escape.
  • Standards are applied.
  • Regulations and legal requirements at the time of implementation.

QCVN 06:2022/BXD and Amendment 1:2023 QCVN 06:2022/BXD continue to be important documents cited by the Ministry of Construction in the relevant guidance on fire safety for houses and works.


12. Assessment process at HRT

Step 1 – Receive application

Determine the premises, location of stairs, shafts, technical rooms and related HVAC systems.

Step 2 – Survey the current status

Check the fan, air duct, damper, intake door, exhaust door and actual operation condition.

Step 3 – Check the system coordination

Evaluate the relationship between:

Booster – smoke extraction – AHU – FCU – Chiller – VRV/VRF – ventilation system.

Step 4 – Propose a plan

Determine items to be inspected, renovated or adjusted according to actual conditions.

Step 5 – Testing and Evaluation

Check the operation status, differential pressure, gas flow and related issues within the actual technical scope.

HRT currently describes its scope as surveying and evaluating HVAC and ventilation systems; the contents of design, approval or acceptance testing specialized fire protection should be determined separately according to the application records and capacity.


13. Conclusion

Stairwell pressurization systems do not simply install a large-capacity fan to blow air into the stairs.

A system that works properly needs coordination:

Fan + wind shaft + feed mouth + damper + pressure outlet + sensor + fire door + smoke extraction + control system.

Special checks are required at both door closed and door open status.

Differential pressure too low may not achieve the smoke control objectives; but differential pressure too high may make it difficult to open the evacuation door. Therefore, the right solution must be based on calculation, design documentation, actual conditions and test results, should not only select the equipment according to the nominal area or flow rate.