What is Low Temperature Difference in Chiller? Cause And
Machine-translated from Vietnamese. Read the original in Vietnamese

Low heat differentials in chillers often indicate that the cold water flow rate and heat exchange load are no longer correlated as designed. If prolonged, Low Delta T can increase pump flow rate, reduce the ability to exploit Chiller capacity and cause energy waste.
What is the Low Heat Difference in Chiller?
In the central chilled-water system, the Chiller generates cold water and delivers it to the AHU, FCU or heat exchanger.
Cold water after receiving heat from the building will return to the Chiller.
The two basic parameters to follow are:
- CHWS – Chilled Water Supply: Temperature chilled-water supply.
- CHWR – Chilled Water Return: Temperature chilled-water return.
Thermal Gap Defined:
ΔT = CHWR – CHWS
For example:
- CHWS = 7°C.
- CHWR = 12°C.
Then:
ΔT = 5 K
If during operation:
- CHWS = 7°C.
- CHWR = 9°C.
then:
ΔT = 2 K
If the system is designed for ΔT around 5–6 K but frequently only reaches 2–3 K, the system may be in a state of Low Delta T – low heat difference.
The important thing is:
Low Delta T doesn't mean the Chiller is broken.
In many cases, the actual cause lies in the water system, pump, control valve, AHU/FCU coil, airflow or BMS control logic.
Why should we care about Delta T's of the Chiller system?
The heat capacity that cold water transports can be expressed as:
Q = ṁ × Cp × ΔT
Where:
- Q: Heat exchanger capacity.
- ṁ: Water volume flow rate.
- Cp: Specific heat of water.
- ΔT: The difference between supply and return water.
From the above formula it can be seen:
With the same cooling load, the lower ΔT, the greater the required water flow rate.
For example:
If the system is operating with:
ΔT = 6 K
but then reduced to:
ΔT = 3 K
then in theory, to transport the same thermal load, the water flow rate could have to be nearly doubled.
This is why Low Delta T can lead to a series of problems in the Chiller Plant.
System signs at risk Low Delta T
Don't just look at ΔT at a time and make a conclusion.
However, if the system appears simultaneously with the following signs, it should be checked:
- CHWR is significantly lower than the design value.
- ΔT maintains low for long time.
- Chilled-water pump frequently runs high speed.
- Actual flow rate is high while the work load is not large.
- Many AHU/FCU valves operate abnormally.
- Differential Pressure maintained too high.
- Chiller must staging more machines soon.
- Pump power's up.
- There are many areas that still lack cold despite the large total flow.
- BMS recorded high flow but Cooling Load did not match.
A rule to remember:
High Flow Does Not Mean High Cooling Capacity.
If cold water passes through the coil heavily but does not receive enough heat, the CHWR remains low and the system Delta T remains reduced.
Common Causes of Low Thermal Spread in Chillers

Low Delta T usually does not result from a single cause.
HRT usually divides causes into 4 groups for easy analysis.
Group 1 – Hydraulic and flow rate problems
This is usually the first group to check in.
Common situations include:
- Water flow rate through coil is too high.
- The cold water valve is too big.
- Oversized select control valve.
- Differential Pressure Setpoint is too high.
- PICV preset sai.
- A bypass or three-way valve allows chilled water to return too early.
What this group has in common is:
Water Flow increases but heat exchange load does not increase accordingly.
Then:
Flow ↑ → ΔT ↓
Water flow rate through coil too high
Assuming an AHU at the present time only needs about 60% of the design load.
In principle, the water flow rate through coil should also be reduced according to demand.
But if the AHU still receives nearly 100% of the design flow rate, the amount of water through the coil will be greater than needed.
Water receives less heat per unit flow rate.
Results:
Low CHWR → ΔT decrease
This is one of the classic causes of Low Delta T.
Cold water valve open too large
A two-way valve adjusts the water flow rate to match the load.
If the load is reduced but the valve is still open large, the coil can receive excess water.
When checking, it is necessary to simultaneously see:
- Valve Position.
- Cooling Demand.
- Zone Temperature.
- Temperature Setpoint.
- Actual Flow.
- Differential Pressure.
Do not deduce:
Valve 70% = Flow 70%
In fact, the relationship between valve opening and flow rate also depends on:
- Valve characteristics.
- Valve Authority.
- Differential pressure qua van.
- Valve dimensions.
- Hydraulic system status.
Select control valve too large
A fairly common design error is that valve selection is primarily based on pipeline DN.
If the valve is too large:
- Small opening but high flow.
- Difficulty controlling part load.
- Valve easy hunting.
- Flow sensitive to ΔP fluctuation.
- Modulation capability decreased.
Control valves should be selected based on:
- Design Flow.
- Pressure Drop.
- Valve Authority.
- Control Characteristic.
- Actual operation conditions.
Do not default:
DN Valve = DN Pipe
Differential Pressure Setpoint too high
In variable flow rate refrigerant systems, the pump is usually controlled by VFD in ΔP.
If ΔP Setpoint is too high:
- Pump Speed increases.
- Terminal near the pump receives residual pressure.
- Flow through the rising valve.
- The valve must close slightly.
- Controls are worse.
Possible sequence:
ΔP high → Flow increase → Over-flow → ΔT decrease → Pump Energy increase
So when processing Low Delta T, it is necessary to check:
ΔP Setpoint ↔ Actual ΔP ↔ Pump Speed ↔ Valve Position ↔ Flow
PICV installed incorrectly
PICV can help limit flow rate and stabilize controllability.
However, PICV is not a system that runs out of Low Delta T.
Common Errors:
- Preset Flow is too high.
- Preset Flow is too low.
- Select the wrong model.
- Not enough minimum ΔP.
- Incorrect actuator control.
- Pump Setpoint is too high.
- The original Design Flow was incorrect.
PICV needs to be commissioned with the entire system.
A bypass or three-way valve allows chilled water to return too early.
Cold water can be directly turned back to the return line through:
- Three-way valve.
- Minimum Flow Bypass.
- Decoupler.
- Uncontrolled bypass.
If the bypass flow rate is too large, the cold water has not received enough heat from the load returned to the Chiller.
Then:
CHWR decrease → ΔT whole system decrease
The question to ask is:
Is the water going through the coil to receive heat, or is the load bypassing?
Group 2 – Coil and Airflow do not exchange enough heat
If the water side has no obvious problem, it is necessary to switch to check the air side.
Coil AHU/FCU poor heat exchanger
Possible causes include:
- Dirty coil.
- Fins is clogged.
- Filter dirty.
- Low airflow.
- Low Fan Speed.
- Damper closed.
- Winds have high pressure loss.
- Actual load is low.
If the coil does not receive enough heat from the air, then the cold water will not be able to heat up as designed.
The sequence to look at is:
Room Load → Airflow → Coil → Water Flow → CHWR
Low Airflow Through Coil
A coil is designed with a specific airflow rate.
If actual airflow is low:
- Heat from the air passes to the water, reducing it.
- The anise water didn't heat up enough.
- CHWR decreases.
- ΔT decrease.
Hence:
Low Delta T can't just check in the Chiller room.
Field AHUs and FCUs must also be evaluated.
Group 3 – Load and Measurement
Low work load
Not all low Delta Ts are faulty.
At times:
- Few people.
- Less operation equipment.
- Low solar load.
- Low outdoor temperatures.
- The new building is partially operational.
The Cooling Load can be very small.
ΔT lower than the design value is possible.
The problem to be concerned about is:
Load has increased but flow is still too high and Delta T remains low for long.
Temperature sensor sai
A small error in CHWS or CHWR can also produce a large error when calculating Delta T.
Need to check:
- Calibration.
- Sensor location.
- How to install sensor.
- Heat exposure.
- Signal for BMS.
- Dislocation between BMS and independent measuring device.
Before making major changes to Pump Speed or Control Logic, it is recommended to verify the measurement data.
Group 4 – TAB and Commissioning are not correct
A well - designed system can still be Low Delta T if not properly commissioned and TAB.
Possible situations include:
- Terminal near the pump receives residual flow.
- Terminal distal lacks flow.
- Balancing valve not adjusted.
- PICV preset sai.
- ΔP Sensor set not suitable.
- Pump Setpoint is too high.
- BMS Control Logic is not optimized.
- Sequencing Chiller is not reasonable.
Low Delta T in this case is indicative of:
Systemic imbalance
Not one device on its own.
How does Low Delta T affect Chiller Plant?
Prolonged low heat gradients can affect both the cold source portion and the distribution system.
Increase water flow rate required
Theo:
Q = ṁ × Cp × ΔT
when ΔT decreases, flow must increase if the same cooling load is to be maintained.
This causes the hydraulic system to transport more water.
Increase pump power
Pump may have to:
- Run at a higher speed.
- Work longer hours.
- Maintain a larger ΔP.
This deprives the Variable Flow and VFD systems of their benefits.
Chiller Plant is limited by flow rate
A dangerous situation is:
Flow is nearing the limit but heat transfer capacity is still below design.
Then the pipeline and pump network can become the limit of the whole plant.
The chiller has power, but it can't be fully exploited.
Early staging chiller
In multiple Chillers, Low Delta T can cause rapid flow.
The control system may have to add a chiller to the operation, although cooling load is not actually required.
Consequences:
- Many Chillers run at part load.
- Increase the number of hours of operation.
- Increase start/stop.
- Plant efficiency decreases.
HVAC Full Power Efficiency Reduced
Do not judge performance by COP of the chiller.
A good performance chiller can still be in an electrically costly operation system if:
- Pumps run fast.
- ΔP is too high.
- Residual Flow.
- Dirty coil.
- The control valve is unstable.
- BMS is not optimized.
Need to see the whole system:
Chiller + Pump + Cooling Tower + AHU/FCU + Control
How to check Low Delta T at Chiller

HRT approach in series:
Cooling Load → CHWS → CHWR → ΔT → Water Flow → Pump → ΔP → Control Valve/PICV → Coil → Airflow → BMS
The goal is to find the cause logically, rather than tailoring each device individually.
Step 1 – Determine the current cooling load
First have to know the system is in:
- Low Load.
- Part Load.
- High Load.
- Peak Load.
The entire part load data should not be taken to compare directly with the Design Condition.
Step 2 – Check for CHWS and CHWR
Recognition:
- CHWS.
- CHWR.
- ΔT.
- Setpoint.
- Trend over time.
It's better to judge by trends than a snapshot.
Step 3 – Compare Design Flow and Actual Flow
This is an important step in identifying over-flow.
Compare:
Design Flow ↔ Actual Flow
For example:
If the load is only about 50–60% but the flow is still 90–100%, the system needs to be deeply tested hydraulically and controlled.
Step 4 – Check the chilled-water pump
Follow up:
- Pump Speed.
- Frequency.
- Flow.
- Head.
- Differential Pressure.
- Number of pumps in operation.
A common mistake is to see the Delta T low and then accelerate the pump.
In many cases:
The pump speed is too high, which contributes to the low Delta T.
Step 5 – Differential Pressure Test
Compare:
ΔP Setpoint ↔ Actual ΔP
Then see the relationship with:
- Pump Speed.
- Valve Position.
- Flow.
- Cooling Demand.
If the majority of valve is closing small but ΔP remains high, Pump Control Strategy should be reviewed.
Step 6 – Check Control Valve and PICV
Need to check:
- Valve Size.
- Valve Position.
- Actuator.
- Preset Flow.
- Minimum ΔP.
- Maximum Flow.
- Control Signal.
- Logic controls.
Valves or actuators should not be replaced before the cause is identified.
Step 7 – Coil Test
Rating:
- Cleanliness coil.
- Wind inlet temperature.
- The temperature of the wind out.
- Airflow.
- Water Flow.
- CHWS.
- CHWR.
Objectives:
Determine if the coil is transferring heat properly to the load.
Step 8 – Check Airflow
Testing:
- Filter.
- Fan Speed.
- Static Pressure.
- Damper.
- Coil Resistance.
- Ductwork.
- Actual Airflow.
The water side and the air side must be evaluated together.
Step 9 – Check BMS and Control Logic
Trends should be analyzed in series:
Load → Setpoint → Sensor → Controller → Output → Valve → Flow → Result
If each device is working but the overall result is still wrong, the problem may be with the coordination of control loops.
Common Mistakes When Handling Low Delta T

Low Delta T is easily mishandled if only a few parameters are seen.
Seeing Low Delta T is Pump Acceleration
If the cause is over-flowing:
Pump Speed ↑ → Flow ↑ → ΔT can continue ↓
Speeding up the pump in this case can make the problem worse.
Chiller Test Only
Low Delta T may derive from:
- AHU.
- FCU.
- Van.
- Pump.
- Sensor.
- BMS.
Don't just focus on the chiller.
Trying to lift CHWR but failing load test
CHWR is not a direct setpoint value.
It is the result of:
Load + Airflow + Water Flow + Heat Transfer
The change in CHWR needs to be addressed to the cause.
Point of View Valve Position
Valve 50% does not mean Flow = 50%.
Actual flow depends on:
- Valve Characteristic.
- Pressure Drop.
- Valve Authority.
- System ΔP.
This is a very common inference error when reading BMS.
Replace PICV and assume that processing is complete
PICV only works properly when:
- Sizing right.
- Preset's right.
- ΔP enough.
- Actuator right.
- Flow design right.
PICV cannot compensate for any design and commissioning errors.
Use a Delta T value for all systems
Not all Chiller systems have the same ΔT design.
The design can be:
- 5 K.
- 6 K.
- 7 K.
- Or another value.
Need to base on the design documentation of each project.
Improvement Solutions Low Delta T
After determining the cause, solutions may include:
- Reduced residual flow.
- Reset Differential Pressure Setpoint.
- Optimized VFD Pump.
- Adjust the PICV preset.
- Select Control Valve again.
- Remove unnecessary bypasses.
- Check the three-way valve.
- Clean the coil.
- Clean the filter.
- Restore airflow.
- TAB back to the system.
- Calibration sensor.
- Optimize BMS.
- Optimal Chiller Sequencing.
- Recommissioning system.
The goal is not to:
Force Delta T up at all costs.
It's about getting the system back to the right relationship:
True Load → True Flow → True Heat Transfer → True ΔT
How does HRT approach Low Delta T?
HRT does not consider Low Delta T to be the Chiller's own fault.
The system is tested in series:
Cooling Load
↓
CHWS
↓
CHWR
↓
ΔT
↓
Water Flow
↓
Pump
↓
Differential Pressure
↓
Control Valve / PICV
↓
Coil
↓
Airflow
↓
BMS
This approach helps distinguish:
- Load problem.
- Hydraulic problems.
- Heat exchanger problems.
- Control issues.
- Measurement problems.
- Commissioning matters.
Then, come up with a solution.
When should you conduct an in-depth survey of your Chiller system?
Should consider inspection when appearing:
- ΔT low elongation.
- Pump Speed is frequently high.
- Larger flow than design.
- HVAC power increased.
- Abnormal chiller staging.
- AHU/FCU lack of refrigeration.
- Valve hunting.
- ΔP high elongation.
- BMS has multiple warnings.
- The post-renovation system was ineffective.
- Long-time system not recommissioning.
A full evaluation should incorporate:
Temperature + Flow + Pressure + Airflow + Control Trend
Don't rely on a single number.
HRT – ESG GREEN HVAC
HRT aims to optimize HVAC system on the basis of:
Understand the right system → Identify the right cause → Correct parameters → Reduce energy waste
The items that can be evaluated include:
- Chiller.
- Pump.
- CHWS / CHWR.
- Delta T.
- Differential Pressure.
- PICV.
- Control Valve.
- AHU.
- FCU.
- Coil.
- Airflow.
- TAB.
- Commissioning.
- BMS.
- Optimize your energy.
The ultimate goal is to:
True load – True flow rate – True control – Optimized energy – sustainable operation.